Plan Review Notes
Plan Review Notes For Permit 17100109
Permit Number 17100109
Review Stop M
Sequence Number 1
Notes
Date Text
2017-11-16 14:31:56PLAN DENIED
 1) SHOW SIZE AND LOCATION OF RETURN AIR
 GRILL FOR 5 TON SYSTEM. SECTION 107 FBC 2014
 2) 18 X 18 RETURN AIR CAN FOR JUMP OVERS
 MUST BE ON THE OTHER SIDE OF THE HALLWAY DOOR
 BY THE AIR HANDLER.
 3) REFER TO SECTION M1602.4 BALANCED RETURN AIR
 IN MASTER BEDROOM SHOULD BE 18" 2014 FBC RESIDENTIAL
 CODE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676