Plan Review Notes
Plan Review Notes For Permit 17100070
Permit Number 17100070
Review Stop B
Sequence Number 1
Notes
Date Text
2017-10-06 18:20:36PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE ROOF SLOPE, ROOF TYPE ( GABLE OR HIP )
 AND THE MEAN ROOF HEIGHT FOR THE STRUCTURE. FBC 107.2.1
  
 2) INDICATE THE SPECIFIC CONCRETE TILE THAT WILL BE
 USED FROM THE ONES THAT ARE LISTED IN THE PRODUCT
 APPROVAL. FBC 107.2.1
  
 3) SPECIFY THE TILE PROFILE AND THE PADDY SIZE AND
 NUMBER OF PADDIES OF ADHESIVE THAT WILL BE USED FROM
 THE AH-160 PRODUCT APPROVAL. THE ALLOWABLE OVERTURNING
 MOMENT HAS TO BE GREATER THAN THE REQUIRED OVERTURNING
 MOMENT FROM THE TILE PRODUCT APPROVAL. FBC 107.2.1
  
 4) THIS STRUCTURE IS LOCATED IN EXPOSURE CATEGORY D
 WITH A 170 MPH VULT WINDSPEED. THE UPLIFT IN THE
 CORNERS (ROOF ZONE 3) EXCEEDS THE MAXIMUM DESIGN
 PRESSURE OF -105 PSF FOR THE CERTAINTEED W-77 ROOF
 SYSTEM SELECTED FOR THE FLAT ROOF. FBC - R 301.2.1
  