2017-12-01 15:45:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 MANY PREVIOUS COMMENTS NOT ADDRESSED, OR NOT ADDRESSED
 SATISFACTORILY. THE PLAN PROVIDED IS SUBSTANTIALLY
 NON-COMPLIANT WITH NEC, THEREFORE, A COMPLETE REVIEW IS
 NOT POSSIBLE. I HAVE LISTED AS MANY ITEMS AS POSSIBLE
 FOR THIS PLAN, BUT FURTHER COMMENTS ARE LIKELY.
  
 1. NOT COMPLIED FROM FIRST REVIEW: VALUE OF WORK STATED
 ON APPLICATION APPEARS LOW. PROVIDE COPY OF SIGNED
 CONTRACT WITH SCOPE OF WORK AND VALUE STATED. FBC 109.3
 (BE ADVISED THAT ANY PROCESS MACHINERY SHOULD NOT BE
 INCLUDED IN THIS VALUE OF WORK, ONLY LABOR AND
 MATERIALS REQUIRED FOR CONSTRUCTION PURPOSES.)
 2. NOT COMPLIED FROM FIRST REVIEW: NEC STATES THAT
 THERE SHALL BE ONLY ONE SERVICE PER BUILDING WITH A
 MAXIMUM OF SIX DISCONNECTS. IT APPEARS YOUR PROPOSED
 INSTALLATION EXCEEDS THIS REQUIREMENT. PROVIDE
 CORRECTION AND/OR CLARIFICATION. NEC 230.2, 230.71; FBC
 107.2.1 MORE DETAIL IS REQUIRED OF EXISTING SERVICE AND
 PANELS TO DETERMINE COMPLIANCE WITH NEC.
 3. NOT COMPLIED FROM FIRST REVIEW: PROVIDE MORE DETAIL
 IN RISER DIAGRAM INCLUDING EXISTING SERVICE WIRE,
 GUTTER, AND CONDUIT SIZES. INCLUDE DETAIL OF GROUNDING
 ELECTRODE SYSTEM AND INTERSYSTEM BONDING TERMINATION
 POINT. NEC 215.5, 250.50, 250.94 WHY IS THERE A CABLE
 TRAY SHOWN ABOVE THE METER CANS? ANY SPLICES MUST BE IN
 AN APPROVED GUTTER/WIREWAY THAT IS RATED FOR OUTDOOR
 LOCATION. FBC 107.2.1, NEC 300.15
 4. NOT CORRECTED FROM FIRST REVIEW: WIRE SIZE SHOWN IN
 RISER DIAGRAM TO THE 400 AMP PANELS IS 2/0 COPPER. THIS
 WIRE IS NOT RATED FOR 400 AMPS. PROVIDE CORRECTION. NEC
 310.15 WIRE SIZE STATED IS STILL NOT RATED FOR 400 AMPS
 AND PLAN SHOWS ONLY ONE WIRE FROM METER DISCONNECT TO
 PANEL AND ONLY TWO WIRES FROM METER TO METER
 DISCONNECT. SIZE WIRE PER NEC.
 5. NOT COMPLIED FROM FIRST REVIEW: PROVIDE THE
 ADDITIONAL LIGHTING CONTROLS STIPULATED IN THE FBC
 ENERGY CODE. IF THIS IS A CHANGE IN OCCUPANCY, ALL
 LIGHTING WILL NEED CONTROLS. FBC CE 405.2.2, 405.2.2.2
 6. NOT COMPLIED SATISFACTORILY FROM FIRST REVIEW:
 PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30 YOU CAN NOT USE
 RESIDENTIAL DEMAND FACTORS FOR COMMERCIAL APPLICATIONS.
 NEC 220
 7. NOT COMPLIED FROM FIRST REVIEW: PROVIDE AVAILABLE
 SHORT CIRCUIT CALCULATION FOR EACH PANEL INCLUDING
 INFORMATION FROM THE POWER COMPANY STATING WHAT THE
 AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO
 CONFIRM THE STATED AIC RATING OF THE SERVICE EQUIPMENT
 AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, 110.10
 8. NOT COMPLIED SATISFACTORILY FROM FIRST REVIEW:
 PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 THE NOTE SUPPLIED ONLY STATES LABEL FOR ARC FLASH
 HAZARD WARNING. PROVIDE CORRECTION.
 9. NOT COMPLIED SATISFACTORILY FROM FIRST REVIEW: PANEL
 SCHEDULES SHOW 2 PANELS NAMED PANEL A AND 2 PANELS
 NAMED PANEL B. EACH PANEL NEEDS A UNIQUE
 IDENTIFICATION. NEC 408.4, 230.2(E) EXISTING PANEL
 SCHEDULES ARE NOT SHOWN. PROVIDE PANELS SCHEDULES FOR
 ALL PANELS IN UNIT WITH A UNIQUE NAME FOR EACH.
 10. COMPLIED.
 11. NOT COMPLIED FROM FIRST REVIEW: THERE IS A BLOCK
 NOTE THAT INDICATES "CONDUIT AND METAL BOXES SHALL MEET
 THE REQUIREMENTS OF NEC 2008". THIS IS NOT THE CURRENT
 CODE. DELETE OR CORRECT. FBC PREFACE.
 12. COMPLIED.
 13. COMPLIED.
 14. NEW COMMENT: THE WIRE SIZE SPECIFIED FROM POWER
 COMPANY IS SHOWS AS 6/0 WIRE, WHICH DOES NOT EXIST.
 DESIGN MUST COMPLY WITH THE NATIONAL ELECTRICAL CODE,
 2011 EDITION.
  
 PLEASE BE ADVISED THAT SOME OF THESE COMMENT HAVE NOT
 BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 A THIRD TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN
 REVIEW WILL BE REQUIRED. FLORIDA STATUTES STATE: ?WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)?
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  