2017-12-01 15:45:38 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| PART VIII ELECTRICAL |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| MANY PREVIOUS COMMENTS NOT ADDRESSED, OR NOT ADDRESSED |
| SATISFACTORILY. THE PLAN PROVIDED IS SUBSTANTIALLY |
| NON-COMPLIANT WITH NEC, THEREFORE, A COMPLETE REVIEW IS |
| NOT POSSIBLE. I HAVE LISTED AS MANY ITEMS AS POSSIBLE |
| FOR THIS PLAN, BUT FURTHER COMMENTS ARE LIKELY. |
| |
| 1. NOT COMPLIED FROM FIRST REVIEW: VALUE OF WORK STATED |
| ON APPLICATION APPEARS LOW. PROVIDE COPY OF SIGNED |
| CONTRACT WITH SCOPE OF WORK AND VALUE STATED. FBC 109.3 |
| (BE ADVISED THAT ANY PROCESS MACHINERY SHOULD NOT BE |
| INCLUDED IN THIS VALUE OF WORK, ONLY LABOR AND |
| MATERIALS REQUIRED FOR CONSTRUCTION PURPOSES.) |
| 2. NOT COMPLIED FROM FIRST REVIEW: NEC STATES THAT |
| THERE SHALL BE ONLY ONE SERVICE PER BUILDING WITH A |
| MAXIMUM OF SIX DISCONNECTS. IT APPEARS YOUR PROPOSED |
| INSTALLATION EXCEEDS THIS REQUIREMENT. PROVIDE |
| CORRECTION AND/OR CLARIFICATION. NEC 230.2, 230.71; FBC |
| 107.2.1 MORE DETAIL IS REQUIRED OF EXISTING SERVICE AND |
| PANELS TO DETERMINE COMPLIANCE WITH NEC. |
| 3. NOT COMPLIED FROM FIRST REVIEW: PROVIDE MORE DETAIL |
| IN RISER DIAGRAM INCLUDING EXISTING SERVICE WIRE, |
| GUTTER, AND CONDUIT SIZES. INCLUDE DETAIL OF GROUNDING |
| ELECTRODE SYSTEM AND INTERSYSTEM BONDING TERMINATION |
| POINT. NEC 215.5, 250.50, 250.94 WHY IS THERE A CABLE |
| TRAY SHOWN ABOVE THE METER CANS? ANY SPLICES MUST BE IN |
| AN APPROVED GUTTER/WIREWAY THAT IS RATED FOR OUTDOOR |
| LOCATION. FBC 107.2.1, NEC 300.15 |
| 4. NOT CORRECTED FROM FIRST REVIEW: WIRE SIZE SHOWN IN |
| RISER DIAGRAM TO THE 400 AMP PANELS IS 2/0 COPPER. THIS |
| WIRE IS NOT RATED FOR 400 AMPS. PROVIDE CORRECTION. NEC |
| 310.15 WIRE SIZE STATED IS STILL NOT RATED FOR 400 AMPS |
| AND PLAN SHOWS ONLY ONE WIRE FROM METER DISCONNECT TO |
| PANEL AND ONLY TWO WIRES FROM METER TO METER |
| DISCONNECT. SIZE WIRE PER NEC. |
| 5. NOT COMPLIED FROM FIRST REVIEW: PROVIDE THE |
| ADDITIONAL LIGHTING CONTROLS STIPULATED IN THE FBC |
| ENERGY CODE. IF THIS IS A CHANGE IN OCCUPANCY, ALL |
| LIGHTING WILL NEED CONTROLS. FBC CE 405.2.2, 405.2.2.2 |
| 6. NOT COMPLIED SATISFACTORILY FROM FIRST REVIEW: |
| PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING |
| AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS |
| ADEQUATE. NEC 215.2, 220, 408.30 YOU CAN NOT USE |
| RESIDENTIAL DEMAND FACTORS FOR COMMERCIAL APPLICATIONS. |
| NEC 220 |
| 7. NOT COMPLIED FROM FIRST REVIEW: PROVIDE AVAILABLE |
| SHORT CIRCUIT CALCULATION FOR EACH PANEL INCLUDING |
| INFORMATION FROM THE POWER COMPANY STATING WHAT THE |
| AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO |
| CONFIRM THE STATED AIC RATING OF THE SERVICE EQUIPMENT |
| AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, 110.10 |
| 8. NOT COMPLIED SATISFACTORILY FROM FIRST REVIEW: |
| PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| THE NOTE SUPPLIED ONLY STATES LABEL FOR ARC FLASH |
| HAZARD WARNING. PROVIDE CORRECTION. |
| 9. NOT COMPLIED SATISFACTORILY FROM FIRST REVIEW: PANEL |
| SCHEDULES SHOW 2 PANELS NAMED PANEL A AND 2 PANELS |
| NAMED PANEL B. EACH PANEL NEEDS A UNIQUE |
| IDENTIFICATION. NEC 408.4, 230.2(E) EXISTING PANEL |
| SCHEDULES ARE NOT SHOWN. PROVIDE PANELS SCHEDULES FOR |
| ALL PANELS IN UNIT WITH A UNIQUE NAME FOR EACH. |
| 10. COMPLIED. |
| 11. NOT COMPLIED FROM FIRST REVIEW: THERE IS A BLOCK |
| NOTE THAT INDICATES "CONDUIT AND METAL BOXES SHALL MEET |
| THE REQUIREMENTS OF NEC 2008". THIS IS NOT THE CURRENT |
| CODE. DELETE OR CORRECT. FBC PREFACE. |
| 12. COMPLIED. |
| 13. COMPLIED. |
| 14. NEW COMMENT: THE WIRE SIZE SPECIFIED FROM POWER |
| COMPANY IS SHOWS AS 6/0 WIRE, WHICH DOES NOT EXIST. |
| DESIGN MUST COMPLY WITH THE NATIONAL ELECTRICAL CODE, |
| 2011 EDITION. |
| |
| PLEASE BE ADVISED THAT SOME OF THESE COMMENT HAVE NOT |
| BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD |
| REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN |
| A THIRD TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN |
| REVIEW WILL BE REQUIRED. FLORIDA STATUTES STATE: ?WITH |
| RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)? |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |