Plan Review Notes
Plan Review Notes For Permit 17100025
Permit Number 17100025
Review Stop P
Sequence Number 1
Notes
Date Text
2017-10-12 13:16:201ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. COMPLY WITH BUILDINGS COMMENT #3 IF THIS A CHANGE OF
 OCCUPANCY A WATER FOUNTAIN COMPLYING WITH FBC ACC 211.2
 AND 602 IS REQUIRED ALSO A SERVICE SINK REQUIRED PER
 FBC PL TABLE 403.1
  
 2. SHT. A-1 PLEASE SHOW CLEAR FLOOR SPACE FOR WATER
 CLOSET AND LAVATORY. PER FBC ACC 604.3.1 AND 606.2
  
 3. FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET. PER FBC ACC 604.6
  
 4. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915
 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP
 OF THE GRIPPING SURFACE, PER FBC ACC 609.4
  
 5. HOT OR TEMPERED WATER IS REQUIRED AT THE LAVATORY.
 PER FBC PL 607.1
  
 6. IF A NEW BACKFLOW IS BEING INSTALLED ON THE WATER
 SERVICE A SEPARATE PERMIT IS REQUIRED IF EXISTING IT
 WILL NEED TO BE RECERTIFIED PLEASE PROVIDE NOTE ON
 PLAN. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  