Plan Review Notes For Permit 17090752 |
Permit Number |
17090752 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2018-01-23 16:04:34 | MECHANICAL REVIEW APPROVED WITH PROVISO: | | | | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS | | SHOWING COMPLIANCE WITH ALL THE REQUIREMENTS OF SEC. | | R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | | | 2- REVISE MASTER BEDROOM TRANSFER DUCT SIZE TO COMPLY | | WITH SEC. M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). | | NOTE: WHEN SIZING THE DUCT KEEP IN MIND THAT NEED TO | | TAKE INTO CONSIDERATION ALL THE SUPPLY AIR THAT IS | | GOING INTO THE MASTER BEDROOM. SEE EXCEPTION #3 OF SEC. | | M1602.4. |
|