Plan Review Notes For Permit 17090752 |
Permit Number |
17090752 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2018-01-22 16:03:03 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1- ENERGY CALCULATIONS ARE TAKING THE CEILING FAN | | CREDIT. REVISE GREAT ROOM CEILING FAN SIZE TO COMPLY | | WITH SEC. R405.7.6 FBC-ENERGY CONSERVATION. | | | | 2- SOIL TEST REPORT SUBMITTED NEEDS THE ENGINEER'S | | ORIGINAL SIGNATURE (NOT COPY). CHAPTER 471 F.S. | | | | 3- PROVIDE PRODUCT APPROVAL FOR THE OVERHEAD GARAGE | | DOOR THAT MEETS THE DESIGN PRESSURES CALCULATED BY THE | | ARCHITECT ON SHEET A-301. (OK. SEE REVISION 18091139) | | | | 4- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT | | APPROVAL. SEC. 107.3.4.1 CITY AMENDMENTS. NOTE: PLEASE | | PLACE THE REVIEW STAMP ON THE FRONT OF THE PRODUCT | | APPROVAL NOT ON THE BACK. | | | | 5- PROVIDE SURVEY (2 COPIES) THAT MATCHES PROPOSED | | HOUSE IN LOT "B" AND THE ADDRESS 245 EDMOR RD. |
|