2017-12-12 16:53:01 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND MECHANICAL |
| REVIEW CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| ORIGINAL COMMENT: |
| 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS |
| SHOWING COMPLIANCE WITH ALL THE REQUIREMENTS OF SEC. |
| R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| |
| ORIGINAL COMMENT: |
| 2- SPECIFY THE SIZE OF THE TRANSFER DUCT FOR THE |
| BALANCED RETURN AIR FOR ALL THE ROOMS ON THE FIRST |
| FLOOR AND ALL THE ROOMS ON THE SECOND FLOOR SHOWING |
| COMPLIANCE WITH SEC. M1602.4 FBC-RESIDENTIAL, 5TH |
| EDITION (2014). |
| NOTE: WHEN SIZING THE DUCT KEEP IN MIND THAT NEED TO |
| TAKE INTO CONSIDERATION ALL THE SUPPLY AIR THAT IS |
| GOING INTO THE MASTER BEDROOM. SEE EXCEPTION #3 OF SEC. |
| M1602.4. |
| |
| RESPONSE: SIZE OF TRANSFER DUCT SPECIFIED FOR THE |
| MASTER BEDROOM DOESN'T COMPLY. REVISE AS REQUIRED. |
| NOTE: KEEP IN MIND THAT NEED TO CONSIDER ALL THE SUPPLY |
| TO THE MASTER BEDROOM, INCLUDING CLOSETS, BATHROOMS, |
| ETC. |
| |
| ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| FOR REFERENCE. |
| |