Plan Review Notes
Plan Review Notes For Permit 17090752
Permit Number 17090752
Review Stop M
Sequence Number 2
Notes
Date Text
2017-12-12 16:53:01NEW SINGLE FAMILY RESIDENCE (R3) SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS
 SHOWING COMPLIANCE WITH ALL THE REQUIREMENTS OF SEC.
 R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 2- SPECIFY THE SIZE OF THE TRANSFER DUCT FOR THE
 BALANCED RETURN AIR FOR ALL THE ROOMS ON THE FIRST
 FLOOR AND ALL THE ROOMS ON THE SECOND FLOOR SHOWING
 COMPLIANCE WITH SEC. M1602.4 FBC-RESIDENTIAL, 5TH
 EDITION (2014).
 NOTE: WHEN SIZING THE DUCT KEEP IN MIND THAT NEED TO
 TAKE INTO CONSIDERATION ALL THE SUPPLY AIR THAT IS
 GOING INTO THE MASTER BEDROOM. SEE EXCEPTION #3 OF SEC.
 M1602.4.
  
 RESPONSE: SIZE OF TRANSFER DUCT SPECIFIED FOR THE
 MASTER BEDROOM DOESN'T COMPLY. REVISE AS REQUIRED.
 NOTE: KEEP IN MIND THAT NEED TO CONSIDER ALL THE SUPPLY
 TO THE MASTER BEDROOM, INCLUDING CLOSETS, BATHROOMS,
 ETC.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]