2017-12-11 11:45:22NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- IT LOOKS LIKE THE REVISED WINDOW FOR BEDROOM #2
 DOESN'T COMPLY WITH THE EGRESS REQUIREMENTS OF SEC.
 R310 FBC-RESIDENTIAL, 5TH EDITION (2014). ACCORDING TO
 THE PGT WINDOWS WEBSITE, THE SIZE OF WINDOWS SPECIFIED
 (SINGLE HUNG 36"X60") DOESN'T COMPLY WITH THE REQUIRED
 HEIGHT CLEAR OPENING AND TOTAL CLEAR OPENING FOR
 WINDOWS ON THE SECOND FLOOR. REVISE AS REQUIRED TO
 COMPLY OR PROVIDE MANUFACTURER'S CUT SHEETS SHOWING
 COMPLIANCE WITH ALL THE CLEAR OPENINGS. NOTE: KEEP IN
 MIND THAT EGRESS NEED TO BE ACCOMPLISHED BY THE NORMAL
 OPERATION OF THE WINDOW WITHOUT ANY ADDITIONAL STEP OR
 KNOWLEDGE TO OBTAIN THE REQUIRED OPENING.
  
 2- SHEET S-2: DESIGN PRESSURES SPECIFIED ON THE ROOF
 FRAMING NOTES FOR ROOF ZONES 2 AND 3 DON'T CORRESPOND
 TO EXPOSURE "D" BASED ON THE MEAN ROOF HEIGHT OF THIS
 TWO STORY BUILDING. REVISE AS REQUIRED. SEC. R301.1 AND
 TABLE R301.2(2) FBC-RESIDENTIAL.
  
 3- ENERGY CALCULATIONS SUBMITTED:
 A) FLOOR INFORMATION ON ITEM #8 IS MISSING THE
 INSULATION R-VALUE BETWEEN THE GARAGE AND THE A/C AREA
 ABOVE. REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
 RESPONSE: REPEAT COMMENT.
  
 NOTE:
 LABEL FOR DOORS AND WINDOWS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL
 BE REQUIRED WHEN THE ENERGY CALCULATIONS DON'T USE THE
 DEFAULT FACTOR FOR GLAZING.
  
 4- NEW COMMENT: REVISED ENERGY CALCULATIONS ARE TAKING
 THE CEILING FAN CREDIT. PLANS NEED TO SPECIFY THE SIZE
 OF ALL CEILING FANS TO VERIFY COMPLIANCE WITH TABLE
 R405.7.6 FBC-ENERGY CONSERVATION.
  
 5- A) SOIL TEST REPORT SUBMITTED NEEDS THE ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS.
 RESPONSE: REPEAT COMMENT. IT LOOKS LIKE THE ENGINEER'S
 SIGNATURE IS NOT ORIGINAL. IT LOOKS LIKE IS THE EXACT
 SAME COPY OF THE SIGNATURE ON ALL REPORTS SUBMITTED.
  
 B) SOIL TEST REPORT SUBMITTED IS MISSING A PLOT PLAN
 SHOWING THE LOCATION OF THE SOIL INVESTIGATION AS
 REQUIRED BY SEC. 1803.6 FBC-BUILDING, 5TH EDITION
 (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED. NOTE: THIS LOT
 WAS SUBDIVIDED ONTO 3 LOTS.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) CLEARLY SPECIFY WHERE ARE THE ETO DOORS DRAWING
 #ET0002 SUBMITTED GOING TO BE INSTALLED. PROVIDE THE
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO
 DRAWINGS SUBMITTED AS REQUESTED ON PREVIOUS CHECKLIST.
 IF THERE IS NOT FLORIDA PRODUCT APPROVAL DOOR
 MANUFACTURER MAY SUBMIT COMPLETE ORIGINAL ENGINEERING
 PACKAGE FOR BUILDING OFFICIAL REVIEW AND APPROVAL. MORE
 INFORMATION WILL BE PROVIDED IF DRAWINGS WILL BE
 SUBMITTED FOR BUILDING OFFICIAL APPROVAL. PLEASE ADVICE
 IF SUBMITTING DRAWINGS FOR BUILDING OFFICIAL REVIEW.
 MORE INFORMATION WILL BE PROVIDED REGARDING THE
 SUBMITTAL PACKAGE.
  
 B) BALCONIES WATERPROOFING UNDERLAYMENT. PROVIDE
 FLORIDA PRODUCT APPROVAL OR MIAMI DADE NOA FOR THE
 MASTERSEAL 550 WATERPROOFING SUBMITTED THIS TIME. NEED
 PRODUCT APPROVAL FOR CONCRETE DECK THAT IS DESIGNED TO
 RECEIVE FINISH FLOOR AS SPECIFIED BY THE ARCHITECT OF
 RECORD. CLEARLY MARK SPECIFIC ASSEMBLY TO BE INSTALLED
 AND PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 FOR ALL DECK ZONES. IF THERE IS NOT PRODUCT APPROVAL,
 MANUFACTURER MAY SUBMIT COMPLETE ORIGINAL ENGINEERING
 PACKAGE FOR BUILDING OFFICIAL APPROVAL. NOTE: THERE ARE
 SEVERAL PRODUCTS THAT ALREADY HAVE A PRODUCT APPROVAL.
 FOR EXAMPLE LOOK AT SEALOFLEX PRODUCTS.
  
 C) ALUMINUM MULLIONS NOA 16-0218.03 SUBMITTED: CLEARLY
 IDENTIFY SIZE OF MULLIONS TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 D) OVERHEAD GARAGE DOOR. NEED PRODUCT APPROVAL FOR DOOR
 THAT MEETS THE DESIGN PRESSURES CALCULATED BY THE
 ARCHITECT ON SHEET A-301.
 RESPONSE: DESIGN PRESSURES OF NOA 15-0826.34 SUBMITTED
 ARE LOWER THAN THE CALCULATED DESIGN PRESSURES.
  
 E) BAHAMA SHUTTERS NOA 15-0316.11 SUBMITTED.
 RESPONSE: PROVIDE PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 F) COLONIAL SHUTTERS AS SPECIFIED ON PLANS. AND,
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 G) PRECAST LINTELS AS SPECIFIED ON PLANS.
 RESPONSE: REPEAT COMMENT.
  
 7- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS. NOTE: PLEASE PLACE THE REVIEW STAMP ON THE
 FRONT OF THE PRODUCT APPROVAL NOT ON THE BACK. THIS IS
 REQUIRED FOR PROPER RECORD RETENTION PURPOSES. WHEN THE
 STAMPS ARE PLACED ON THE BACK OF THE PRODUCT APPROVAL,
 THEY DON'T GET SCANNED. SEC. 107.2.1.4 CITY AMENDMENTS.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 THE COLONIAL SHUTTERS INSTALLATION SPECS SUBMITTED
 PRIOR TO SUBMITTAL TO THIS OFFICE. SEC. 107.3.4.2 CITY
 AMENDMENTS.
  
 9- THERE ARE TOO MANY PRODUCT APPROVALS SUBMITTED.
 CLEARLY MARK ON EACH PRODUCT APPROVAL LOCATION WHERE
 THE DOOR OR WINDOW IS GOING TO BE INSTALLED. REMOVE ALL
 PRODUCT APPROVALS THAT ARE NOT GOING TO BE USED TO
 AVOID CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS.
  
 10- ONE SET OF PLANS SUBMITTED IS MISSING DRAWING M201
 AND S-4. PROVIDE 2 COMPLETE SETS. SEC. 107.1 CITY
 AMENDMENTS.
  
 11- SURVEY SUBMITTED: REVISE THE FLOOD INFORMATION. THE
 NEW FLOOD MAPS WENT INTO EFFECT ON OCTOBER 5TH 2017.
 PROVIDE ALL THE FLOOD INFORMATION BASED ON THE CURRENT
 FLOOD MAPS TO AVOID CONFLICTS. SEC. 107.2.1 CITY
 AMENDMENTS. (NOTE: SURVEY SPECIFIED IS INCORRECT ALSO.
 ACCORDING TO MAP DATED MARCH 1, 1979 THIS PROPERTY WAS
 LOCATED IN FLOOD ZONE "C" NOT "B").
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  