Date |
Text |
2017-12-11 11:45:22 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- IT LOOKS LIKE THE REVISED WINDOW FOR BEDROOM #2 |
| DOESN'T COMPLY WITH THE EGRESS REQUIREMENTS OF SEC. |
| R310 FBC-RESIDENTIAL, 5TH EDITION (2014). ACCORDING TO |
| THE PGT WINDOWS WEBSITE, THE SIZE OF WINDOWS SPECIFIED |
| (SINGLE HUNG 36"X60") DOESN'T COMPLY WITH THE REQUIRED |
| HEIGHT CLEAR OPENING AND TOTAL CLEAR OPENING FOR |
| WINDOWS ON THE SECOND FLOOR. REVISE AS REQUIRED TO |
| COMPLY OR PROVIDE MANUFACTURER'S CUT SHEETS SHOWING |
| COMPLIANCE WITH ALL THE CLEAR OPENINGS. NOTE: KEEP IN |
| MIND THAT EGRESS NEED TO BE ACCOMPLISHED BY THE NORMAL |
| OPERATION OF THE WINDOW WITHOUT ANY ADDITIONAL STEP OR |
| KNOWLEDGE TO OBTAIN THE REQUIRED OPENING. |
| |
| 2- SHEET S-2: DESIGN PRESSURES SPECIFIED ON THE ROOF |
| FRAMING NOTES FOR ROOF ZONES 2 AND 3 DON'T CORRESPOND |
| TO EXPOSURE "D" BASED ON THE MEAN ROOF HEIGHT OF THIS |
| TWO STORY BUILDING. REVISE AS REQUIRED. SEC. R301.1 AND |
| TABLE R301.2(2) FBC-RESIDENTIAL. |
| |
| 3- ENERGY CALCULATIONS SUBMITTED: |
| A) FLOOR INFORMATION ON ITEM #8 IS MISSING THE |
| INSULATION R-VALUE BETWEEN THE GARAGE AND THE A/C AREA |
| ABOVE. REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| |
| B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| RESPONSE: REPEAT COMMENT. |
| |
| NOTE: |
| LABEL FOR DOORS AND WINDOWS SHOWING THE U-FACTOR AND |
| SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL |
| BE REQUIRED WHEN THE ENERGY CALCULATIONS DON'T USE THE |
| DEFAULT FACTOR FOR GLAZING. |
| |
| 4- NEW COMMENT: REVISED ENERGY CALCULATIONS ARE TAKING |
| THE CEILING FAN CREDIT. PLANS NEED TO SPECIFY THE SIZE |
| OF ALL CEILING FANS TO VERIFY COMPLIANCE WITH TABLE |
| R405.7.6 FBC-ENERGY CONSERVATION. |
| |
| 5- A) SOIL TEST REPORT SUBMITTED NEEDS THE ENGINEER'S |
| ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 |
| FLORIDA STATUTE WHEN SUBMITTING DOCUMENTS FOR PUBLIC |
| RECORDS. |
| RESPONSE: REPEAT COMMENT. IT LOOKS LIKE THE ENGINEER'S |
| SIGNATURE IS NOT ORIGINAL. IT LOOKS LIKE IS THE EXACT |
| SAME COPY OF THE SIGNATURE ON ALL REPORTS SUBMITTED. |
| |
| B) SOIL TEST REPORT SUBMITTED IS MISSING A PLOT PLAN |
| SHOWING THE LOCATION OF THE SOIL INVESTIGATION AS |
| REQUIRED BY SEC. 1803.6 FBC-BUILDING, 5TH EDITION |
| (2014). |
| RESPONSE: REPEAT COMMENT. NOT ADDRESSED. NOTE: THIS LOT |
| WAS SUBDIVIDED ONTO 3 LOTS. |
| |
| 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| A) CLEARLY SPECIFY WHERE ARE THE ETO DOORS DRAWING |
| #ET0002 SUBMITTED GOING TO BE INSTALLED. PROVIDE THE |
| FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO |
| DRAWINGS SUBMITTED AS REQUESTED ON PREVIOUS CHECKLIST. |
| IF THERE IS NOT FLORIDA PRODUCT APPROVAL DOOR |
| MANUFACTURER MAY SUBMIT COMPLETE ORIGINAL ENGINEERING |
| PACKAGE FOR BUILDING OFFICIAL REVIEW AND APPROVAL. MORE |
| INFORMATION WILL BE PROVIDED IF DRAWINGS WILL BE |
| SUBMITTED FOR BUILDING OFFICIAL APPROVAL. PLEASE ADVICE |
| IF SUBMITTING DRAWINGS FOR BUILDING OFFICIAL REVIEW. |
| MORE INFORMATION WILL BE PROVIDED REGARDING THE |
| SUBMITTAL PACKAGE. |
| |
| B) BALCONIES WATERPROOFING UNDERLAYMENT. PROVIDE |
| FLORIDA PRODUCT APPROVAL OR MIAMI DADE NOA FOR THE |
| MASTERSEAL 550 WATERPROOFING SUBMITTED THIS TIME. NEED |
| PRODUCT APPROVAL FOR CONCRETE DECK THAT IS DESIGNED TO |
| RECEIVE FINISH FLOOR AS SPECIFIED BY THE ARCHITECT OF |
| RECORD. CLEARLY MARK SPECIFIC ASSEMBLY TO BE INSTALLED |
| AND PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF |
| THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES |
| FOR ALL DECK ZONES. IF THERE IS NOT PRODUCT APPROVAL, |
| MANUFACTURER MAY SUBMIT COMPLETE ORIGINAL ENGINEERING |
| PACKAGE FOR BUILDING OFFICIAL APPROVAL. NOTE: THERE ARE |
| SEVERAL PRODUCTS THAT ALREADY HAVE A PRODUCT APPROVAL. |
| FOR EXAMPLE LOOK AT SEALOFLEX PRODUCTS. |
| |
| C) ALUMINUM MULLIONS NOA 16-0218.03 SUBMITTED: CLEARLY |
| IDENTIFY SIZE OF MULLIONS TO BE INSTALLED TO VERIFY |
| COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES. |
| RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| |
| D) OVERHEAD GARAGE DOOR. NEED PRODUCT APPROVAL FOR DOOR |
| THAT MEETS THE DESIGN PRESSURES CALCULATED BY THE |
| ARCHITECT ON SHEET A-301. |
| RESPONSE: DESIGN PRESSURES OF NOA 15-0826.34 SUBMITTED |
| ARE LOWER THAN THE CALCULATED DESIGN PRESSURES. |
| |
| E) BAHAMA SHUTTERS NOA 15-0316.11 SUBMITTED. |
| RESPONSE: PROVIDE PROVIDE COMPLETE INSTALLATION |
| SCHEDULE. SEE CITY SAMPLE. |
| |
| F) COLONIAL SHUTTERS AS SPECIFIED ON PLANS. AND, |
| PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY |
| SAMPLE. |
| RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| |
| G) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| RESPONSE: REPEAT COMMENT. |
| |
| 7- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL PRODUCT |
| APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| AMENDMENTS. NOTE: PLEASE PLACE THE REVIEW STAMP ON THE |
| FRONT OF THE PRODUCT APPROVAL NOT ON THE BACK. THIS IS |
| REQUIRED FOR PROPER RECORD RETENTION PURPOSES. WHEN THE |
| STAMPS ARE PLACED ON THE BACK OF THE PRODUCT APPROVAL, |
| THEY DON'T GET SCANNED. SEC. 107.2.1.4 CITY AMENDMENTS. |
| |
| 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| THE COLONIAL SHUTTERS INSTALLATION SPECS SUBMITTED |
| PRIOR TO SUBMITTAL TO THIS OFFICE. SEC. 107.3.4.2 CITY |
| AMENDMENTS. |
| |
| 9- THERE ARE TOO MANY PRODUCT APPROVALS SUBMITTED. |
| CLEARLY MARK ON EACH PRODUCT APPROVAL LOCATION WHERE |
| THE DOOR OR WINDOW IS GOING TO BE INSTALLED. REMOVE ALL |
| PRODUCT APPROVALS THAT ARE NOT GOING TO BE USED TO |
| AVOID CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 10- ONE SET OF PLANS SUBMITTED IS MISSING DRAWING M201 |
| AND S-4. PROVIDE 2 COMPLETE SETS. SEC. 107.1 CITY |
| AMENDMENTS. |
| |
| 11- SURVEY SUBMITTED: REVISE THE FLOOD INFORMATION. THE |
| NEW FLOOD MAPS WENT INTO EFFECT ON OCTOBER 5TH 2017. |
| PROVIDE ALL THE FLOOD INFORMATION BASED ON THE CURRENT |
| FLOOD MAPS TO AVOID CONFLICTS. SEC. 107.2.1 CITY |
| AMENDMENTS. (NOTE: SURVEY SPECIFIED IS INCORRECT ALSO. |
| ACCORDING TO MAP DATED MARCH 1, 1979 THIS PROPERTY WAS |
| LOCATED IN FLOOD ZONE "C" NOT "B"). |
| |
| |
| ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| FOR REFERENCE. |
| |