Plan Review Notes For Permit 17090752 |
Permit Number |
17090752 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-10-24 16:38:25 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW | | COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- PLANS SUBMITTED HAVE A COPY OF THE SEAL AND | | SIGNATURE. ALL PLANS NEED TO HAVE THE ORIGINAL | | SIGNATURE OF THE ARCHITECT AS REQUIRED BY CHAPTER 481 | | WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. | | | | 2- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS | | SHOWING COMPLIANCE WITH ALL THE REQUIREMENTS OF SEC. | | R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | | | 3- SPECIFY THE SIZE OF THE TRANSFER DUCT FOR THE | | BALANCED RETURN AIR FOR ALL THE ROOMS ON THE FIRST | | FLOOR AND ALL THE ROOMS ON THE SECOND FLOOR SHOWING | | COMPLIANCE WITH SEC. M1602.4 FBC-RESIDENTIAL, 5TH | | EDITION (2014). | | NOTE: WHEN SIZING THE DUCT KEEP IN MIND THAT NEED TO | | TAKE INTO CONSIDERATION ALL THE SUPPLY AIR THAT IS | | GOING INTO THE MASTER BEDROOM. SEE EXCEPTION #3 OF SEC. | | M1602.4. | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS | | FOR REFERENCE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|