Plan Review Notes
Plan Review Notes For Permit 17090752
Permit Number 17090752
Review Stop E
Sequence Number 1
Notes
Date Text
2017-10-20 10:53:16 
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS REQUIRED
 WITHIN 3 FEET OF EACH BASIN. PROVIDE CORRECTION.
 NEC 210.11(C)(3), 210.52(D); FBC RE 3703.4, 3901.6
 PAGE E-101 GUEST STUDY BATHROOM, PAGE E-102 BEDROOM #2
 BATHROOM
  
 PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN GARAGE. NEC
 210.8; FBC RE3902.2
 INCLUDES GARAGE DOOR OPENER.
  
 SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN
 6 FEET FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION.
 NEC 210.52; FBC RE3901.2.1
 PAGE E-101 GREAT ROOM, PAGE E-102 MASTER SUTIE, BEDROOM
 #2
  
 PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER
 CODE. SHOW ON PLAN ALL EXISTING ALARMS.
 IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS NEW
 INSTALLATIONS. FBC R314.3, FBC 107.2
 PAGE E-102 TOP OF STAIRS AND MEDIA LOFT WHICH IS WITHIN
 10' OF SLEEPING AREAS.
  
 SHOW LOCATION OF SERVICE AND PANELS, NO LOCATION SHOWN.
 FBC RE3601.6.2 SERVICE DISCONNECT LOCATION.
 PAGE E-101
  
 CORD-CONNECTED LUMINAIRES, CHAIN-, CABLE-, OR
 CORD-SUSPENDED-LUMINAIRES, LIGHTING TRACK, PENDANTS,
 AND CEILING-SUSPENDED (PADDLE) FANS SHALL NOT HAVE ANY
 PARTS LOCATED WITHIN A ZONE MEASURED 3 FEET
 (914 MM) HORIZONTALLY AND 8 FEET (2438 MM) VERTICALLY
 FROM THE TOP OF A BATHTUB RIM FBC RE4003.11
 LIGHT OVER TUB ON PAGE E-102
  
 ALL CIRCUITS AND CIRCUIT MODIFICATIONS SHALL BE LEGIBLY
 IDENTIFIED AS TO THEIR CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED
 FROM ALL OTHERS. SPARE POSITIONS THAT CONTAIN UNUSED
 OVERCURRENT DEVICES OR SWITCHES SHALL BE DESCRIBED
 ACCORDINGLY. THE IDENTIFICATION SHALL BE INCLUDED IN A
 CIRCUIT DIRECTORY LOCATED ON THE FACE OF THE
 PANELBOARD ENCLOSURE OR INSIDE THE PANEL DOOR. CIRCUITS
 SHALL NOT BE DESCRIBED IN A MANNER THAT DEPENDS
 ON TRANSIENT CONDITIONS OF OCCUPANCY. FBC RE3706.2
 PANEL SCHEDULES NOT DESCRIPTIVE ENOUGH FOR CIRCUITS.