| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED |
| NFPA 70 2011 EDITION |
| |
| JAKE LEAHY |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| |
| A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS REQUIRED |
| WITHIN 3 FEET OF EACH BASIN. PROVIDE CORRECTION. |
| NEC 210.11(C)(3), 210.52(D); FBC RE 3703.4, 3901.6 |
| PAGE E-101 GUEST STUDY BATHROOM, PAGE E-102 BEDROOM #2 |
| BATHROOM |
| |
| PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN GARAGE. NEC |
| 210.8; FBC RE3902.2 |
| INCLUDES GARAGE DOOR OPENER. |
| |
| SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING |
| REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN |
| 6 FEET FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. |
| NEC 210.52; FBC RE3901.2.1 |
| PAGE E-101 GREAT ROOM, PAGE E-102 MASTER SUTIE, BEDROOM |
| #2 |
| |
| PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER |
| CODE. SHOW ON PLAN ALL EXISTING ALARMS. |
| IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS NEW |
| INSTALLATIONS. FBC R314.3, FBC 107.2 |
| PAGE E-102 TOP OF STAIRS AND MEDIA LOFT WHICH IS WITHIN |
| 10' OF SLEEPING AREAS. |
| |
| SHOW LOCATION OF SERVICE AND PANELS, NO LOCATION SHOWN. |
| FBC RE3601.6.2 SERVICE DISCONNECT LOCATION. |
| PAGE E-101 |
| |
| CORD-CONNECTED LUMINAIRES, CHAIN-, CABLE-, OR |
| CORD-SUSPENDED-LUMINAIRES, LIGHTING TRACK, PENDANTS, |
| AND CEILING-SUSPENDED (PADDLE) FANS SHALL NOT HAVE ANY |
| PARTS LOCATED WITHIN A ZONE MEASURED 3 FEET |
| (914 MM) HORIZONTALLY AND 8 FEET (2438 MM) VERTICALLY |
| FROM THE TOP OF A BATHTUB RIM FBC RE4003.11 |
| LIGHT OVER TUB ON PAGE E-102 |
| |
| ALL CIRCUITS AND CIRCUIT MODIFICATIONS SHALL BE LEGIBLY |
| IDENTIFIED AS TO THEIR CLEAR, EVIDENT, AND SPECIFIC |
| PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE |
| SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| DISTINGUISHED |
| FROM ALL OTHERS. SPARE POSITIONS THAT CONTAIN UNUSED |
| OVERCURRENT DEVICES OR SWITCHES SHALL BE DESCRIBED |
| ACCORDINGLY. THE IDENTIFICATION SHALL BE INCLUDED IN A |
| CIRCUIT DIRECTORY LOCATED ON THE FACE OF THE |
| PANELBOARD ENCLOSURE OR INSIDE THE PANEL DOOR. CIRCUITS |
| SHALL NOT BE DESCRIBED IN A MANNER THAT DEPENDS |
| ON TRANSIENT CONDITIONS OF OCCUPANCY. FBC RE3706.2 |
| PANEL SCHEDULES NOT DESCRIPTIVE ENOUGH FOR CIRCUITS. |