2017-10-23 12:33:06NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PLANS SUBMITTED HAVE A COPY OF THE SEAL AND
 SIGNATURE. ALL PLANS NEED TO HAVE THE ORIGINAL
 SIGNATURE OF THE ARCHITECT AS REQUIRED BY CHAPTER 481
 WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
  
 3- IT LOOKS LIKE THE CASEMENT WINDOWS SPECIFIED FOR THE
 GUEST BEDROOM AND BEDROOM #2 DON'T COMPLY WITH THE
 EGRESS REQUIREMENTS OF SEC. R310 FBC-RESIDENTIAL, 5TH
 EDITION (2014). ACCORDING TO THE PGT WINDOWS WEBSITE,
 THE SIZE OF WINDOWS SPECIFIED DON'T COMPLY WITH THE
 REQUIRED WIDTH CLEAR OPENING AND TOTAL CLEAR OPENING.
 REVISE AS REQUIRED TO COMPLY OR PROVIDE MANUFACTURER'S
 CUT SHEETS SHOWING COMPLIANCE WITH ALL THE CLEAR
 OPENINGS. NOTE: KEEP IN MIND THAT EGRESS NEED TO BE
 ACCOMPLISHED BY THE NORMAL OPERATION OF THE WINDOW
 WITHOUT ANY ADDITIONAL STEP OR KNOWLEDGE TO OBTAIN THE
 REQUIRED OPENING.
  
 4- SPECIFY SELF CLOSING DEVICE FOR THE GARAGE DOOR
 LEADING TO THE INTERIOR OF THE HOUSE AS REQUIRED BY
 SEC. R302.5.1 FBC-RESIDENTIAL.
  
 5- ENGINEERING CRITERIA ON THE NEW CONSTRUCTION NOTES
 ON SHEET A-301 SPECIFIES R2. THIS IS A SINGLE FAMILY
 RESIDENCE, THEREFORE THE CORRECT OCCUPANCY
 CLASSIFICATION IS R3. REVISE AS REQUIRED. SEC. 310.5
 FBC-BUILDING, 5TH EDITION (2014).
  
 6- SPECIFY CARBON MONOXIDE ALARMS ON THE SECOND FLOOR
 ON THE LOCATION REQUIRED BY SEC. R315.1
 FBC-RESIDENTIAL. NOTE: ELECTRICAL PLAN FOR THE FIRST
 FLOOR SHOWS SMOKE AND ALARMS AND CARBON MONOXIDE ALARMS
 COMBO, BUT SECOND FLOOR PLAN ONLY SHOWS SMOKE ALARMS.
  
 7- SIZE OF FOOTINGS SHOWN ON SHEET S-1 DON'T MATCH
 SIZES SHOWN ON THE WALL SECTIONS ON SHEET A-402. REVISE
 AS REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 8- SPACING OF THE ANCHORS SHOWN ON THE LEDGER TABLE ON
 SHEET S-2 AND S-3 DOESN'T MATCH SPACING SHOWN ON THE
 TWO STORY WALL SECTION SHOWN ON SHEET A-402. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 9- SPECIFY ATTIC ACCESS LOCATION AND SIZE SHOWING
 COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL.
  
 10- BUILDING EXPOSURE SPECIFIED ON ROOF FRAMING NOTES
 ON SHEETS S-2 AND S-3 DOESN'T MATCH THE EXPOSURE
 SPECIFIED ON THE NEW CONSTRUCTION NOTES ON SHEET A-301.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 11- CLARIFY WHY THE DESIGN PRESSURES SHOWN ON SHEETS
 S-2 AND S-3 ARE BASED ON 20 S.F TRIBUTARY AREA. PROVIDE
 THE DESIGN PRESSURES BASED ON THE ACTUAL EFFECTIVE AREA
 OR USE THE LOAD ASSOCIATED WITH THE LOWER EFFECTIVE
 AREA. SEE NOTE "B" OF TABLE R301.2(2) FC-RESIDENTIAL.
 NOTE: COORDINATE DESIGN PRESSURES WITH THOSE SHOWN ON
 SHEET A-301.
 CLARIFY WHY THE DESIGN PRESSURES FOR THE DOORS ARE
 HIGHER THAN THE DESIGN PRESSURES FOR THE WINDOWS.
 TYPICALLY, THE SMALLER THE OPENING THE HIGHER THE
 DESIGN PRESSURES.
  
 12- PROVIDE DETAILS AND SPECIFICATIONS FOR THE
 CONNECTION AT TOP AND BOTTOM OF STEEL COLUMN LOCATED BY
 THE GARAGE AREA AND GOING ALL THE WAY UP TO THE ROOF
 FRAMING. SEC. R301.1 FBC-RESIDENTIAL.
  
 13- SPECIFY DOUBLE LAYER OF WATER RESISTIVE BARRIER FOR
 WOOD FRAMED WALL WITH STUCCO AS REQUIRED BY SEC.
 R703.6.3 FBC-RESIDENTIAL.
  
 14- REVISE STUCCO THICKNESS SPECIFIED ON ALL WALL
 SECTIONS. NEED 7/8" MIN. THICKNESS NOT 5/8" AS REQUIRED
 BY TABLE R702.1(1) FBC-RESIDENTIAL.
  
 15- ENERGY CALCULATIONS SUBMITTED:
 A) AREAS SHOWN ON ITEM #8 DON'T MATCH ARCHITECTURAL
 PLANS SHEET A-101. REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). NOTE: CHECK FIRST FLOOR AREA AND SECOND FLOOR
 AREA.
  
 B) FLOOR INFORMATION ON ITEM #8 IS MISSING THE
 INSULATION R-VALUE BETWEEN THE GARAGE AND THE A/C AREA
 ABOVE. REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 C) THE AREA SHOWN ON THE "SPACES" INFORMATION ON PAGE 2
 OF 5 DOESN'T MATCH PLANS. COORDINATE WITH ITEM #15(A)
 ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) ROOF MATERIAL SHOWN ON PAGE 2 OF 5 DOESN'T MATCH
 PLANS. REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 E) THE VENT RATIO SHOWN ON PAGE 2 OF 5 IS 1/300.
 ARCHITECTURAL PLANS DON'T SPECIFY THIS VENT RATIO.
 PERSON PREPARING THE ENERGY CALCULATIONS TO PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE
 WITH THE 1/300 RATIO AS REQUIRED BY THE EXCEPTION OF
 SEC. R806.2 FBC-RESIDENTIAL. OR, SPECIFY THE TYPICAL
 1/150 VENT RATIO.
  
 F) CEILING AREAS SHOWN ON PAGE 3 OF 5 DON'T MATCH
 PLANS. REVISE AS REQUIRED. WHERE ARE THESE AREAS TAKEN
 FROM?. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G) DOORS INFORMATION SHOWN ON PAGE 3 OF 5 DOESN'T MATCH
 PLANS AND PRODUCT APPROVALS SUBMITTED. REVISE AS
 REQUIRED. THE SIZE DOESN'T MATCH PLANS AND THIS IS A
 DOOR WITH GLASS. DOORS WITH GLASS NEED TO BE CONSIDERED
 IN THE GLAZING (WINDOWS) AREA AS REQUIRED BY SEC.
 R405.5.3.3 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H) WINDOWS INFORMATION SHOWN ON PAGE 3 OF 5 DOESN'T
 MATCH PLANS. REVISE AS REQUIRED. NOTE: REVISE THE
 ORIENTATION, AREA AND OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I) GARAGE FLOOR AREA SHOWN ON PAGE 4 OF 5 DOESN'T MATCH
 AREA SHOWN ON PLANS. REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 J) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 NOTE:
 LABEL FOR DOORS AND WINDOWS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL
 BE REQUIRED WHEN THE ENERGY CALCULATIONS DON'T USE THE
 DEFAULT FACTOR FOR GLAZING.
  
 16- A) SOIL TEST REPORT SUBMITTED NEEDS THE ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS.
  
 B) SOIL TEST REPORT SUBMITTED IS MISSING A PLOT PLAN
 SHOWING THE LOCATION OF THE SOIL INVESTIGATION AS
 REQUIRED BY SEC. 1803.6 FBC-BUILDING, 5TH EDITION
 (2014).
  
 17- PROVIDE COMPLETE WALL SECTIONS AND SPECIFICATIONS
 FOR THE CONSTRUCTION OF THE CONCRETE BALCONIES AS SHOWN
 ON PLANS. SEC. R301.1 FBC-RESIDENTIAL. NOTE: ALSO
 SPECIFY FLOOR FINISH. THIS IS REQUIRED TO VERIFY
 COMPLIANCE OF THE UNDERLAYMENT PRODUCT APPROVAL.
  
 18- PROVIDE COMPLETE SECTION/DETAIL AND SPECIFICATIONS
 FOR THE INSTALLATION OF THE DECORATIVE SHUTTERS SHOWN
 ON THE FRONT ELEVATION ON THE SECOND FLOOR COVERED
 BALCONY. SEC. R301.1 FBC-RESIDENTIAL.
  
 19- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ENTRY DOOR WITH SIDELITE AS SHOWN ON PLANS. NOTE:
 NEED PRODUCT APPROVAL FOR DOOR THAT MEETS OR EXCEEDS
 THE DESIGN PRESSURES CALCULATED BY THE ARCHITECT ON
 SHEET A-301. AND NEED TO PROVIDE FLORIDA PRODUCT
 APPROVAL COVER PAGE THAT CORRESPONDS TO DRAWING #:
 ET0002 SUBMITTED. SUBMIT TWO COPIES. ONLY ONE WAS
 SUBMITTED.
  
 B) MODIFIED BITUMEN FOR BALCONIES UNDERLAYMENT. NOA
 12-0703.06 SUBMITTED IS FOR WOOD DECKS. NEED PRODUCT
 APPROVAL FOR CONCRETE DECK THAT IS DESIGNED TO RECEIVE
 FINISH FLOOR AS SPECIFIED BY THE ARCHITECT OF RECORD.
 NOTE: CLEARLY MARK SPECIFIC ASSEMBLY TO BE INSTALLED
 AND PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 FOR ALL DECK ZONES.
  
 C) PEEL AND STICK UNDERLAYMENT AS SPECIFIED ON
 PLANS/DETAILS. ROOFING UNDERLAYMENT NOA 16-1116.09
 SUBMITTED: CLEARLY MARK WHICH APPROVED UNDERLAYMENT
 ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE PROPOSED INSTALLATION.
  
 D) METAL ROOF AS SPECIFIED ON PLANS.
  
 E) ALUMINUM MULLIONS NOA 16-0218.03 SUBMITTED: CLEARLY
 IDENTIFY SIZE OF MULLIONS AND WHERE IS GOING TO BE
 INSTALLED.
  
 F) THERE ARE DIFFERENT NOA'S SUBMITTED FOR THE FRENCH
 DOORS. NOA 16-0629.16 AND NOA 16-0629.17. CLEARLY MARK
 WHERE EACH DOOR IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES.
  
 G) OVERHEAD GARAGE DOOR. NEED PRODUCT APPROVAL FOR DOOR
 THAT MEETS THE DESIGN PRESSURES CALCULATED BY THE
 ARCHITECT ON SHEET A-301. AND, PROVIDE COPY OF FLORIDA
 PRODUCT APPROVAL COVER PAGE THAT CORRESPONDS TO
 DRAWINGS SUBMITTED.
  
 H) GARAGE SIDE DOOR. NEED PRODUCT APPROVAL FOR DOOR
 THAT MEETS THE DESIGN PRESSURES CALCULATED BY THE
 ARCHITECT ON SHEET A-301. AND, PROVIDE COPY OF FLORIDA
 PRODUCT APPROVAL COVER PAGE THAT CORRESPONDS TO
 DRAWINGS SUBMITTED.
  
 I) BAHAMA SHUTTERS AS SPECIFIED ON PLANS. AND, PROVIDE
 COMPLETE INSTALLATION SCHEDULE. SEE CITY SAMPLE.
  
 J) COLONIAL SHUTTERS AS SPECIFIED ON PLANS. AND,
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
  
 K) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 L) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR.
  
 20- ARCHITECT OF RECORD TO REVIEW AND APPROVE ALL
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS. NOTE: PLEASE PLACE THE REVIEW STAMP ON THE
 FRONT OF THE PRODUCT APPROVAL NOT ON THE BACK. THIS IS
 REQUIRED FOR PROPER RECORD RETENTION PURPOSES. WHEN THE
 STAMPS ARE PLACED ON THE BACK OF THE PRODUCT APPROVAL,
 THEY DON'T GET SCANNED. SEC. 107.2.1.4 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT