2017-10-23 12:33:06 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| COUNTY (2300 N. JOG RD) FOR IMPACT FEE ASSESSMENT. |
| BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| THE UNIFIED LAND DEVELOPMENT CODE. |
| |
| 2- PLANS SUBMITTED HAVE A COPY OF THE SEAL AND |
| SIGNATURE. ALL PLANS NEED TO HAVE THE ORIGINAL |
| SIGNATURE OF THE ARCHITECT AS REQUIRED BY CHAPTER 481 |
| WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. |
| |
| 3- IT LOOKS LIKE THE CASEMENT WINDOWS SPECIFIED FOR THE |
| GUEST BEDROOM AND BEDROOM #2 DON'T COMPLY WITH THE |
| EGRESS REQUIREMENTS OF SEC. R310 FBC-RESIDENTIAL, 5TH |
| EDITION (2014). ACCORDING TO THE PGT WINDOWS WEBSITE, |
| THE SIZE OF WINDOWS SPECIFIED DON'T COMPLY WITH THE |
| REQUIRED WIDTH CLEAR OPENING AND TOTAL CLEAR OPENING. |
| REVISE AS REQUIRED TO COMPLY OR PROVIDE MANUFACTURER'S |
| CUT SHEETS SHOWING COMPLIANCE WITH ALL THE CLEAR |
| OPENINGS. NOTE: KEEP IN MIND THAT EGRESS NEED TO BE |
| ACCOMPLISHED BY THE NORMAL OPERATION OF THE WINDOW |
| WITHOUT ANY ADDITIONAL STEP OR KNOWLEDGE TO OBTAIN THE |
| REQUIRED OPENING. |
| |
| 4- SPECIFY SELF CLOSING DEVICE FOR THE GARAGE DOOR |
| LEADING TO THE INTERIOR OF THE HOUSE AS REQUIRED BY |
| SEC. R302.5.1 FBC-RESIDENTIAL. |
| |
| 5- ENGINEERING CRITERIA ON THE NEW CONSTRUCTION NOTES |
| ON SHEET A-301 SPECIFIES R2. THIS IS A SINGLE FAMILY |
| RESIDENCE, THEREFORE THE CORRECT OCCUPANCY |
| CLASSIFICATION IS R3. REVISE AS REQUIRED. SEC. 310.5 |
| FBC-BUILDING, 5TH EDITION (2014). |
| |
| 6- SPECIFY CARBON MONOXIDE ALARMS ON THE SECOND FLOOR |
| ON THE LOCATION REQUIRED BY SEC. R315.1 |
| FBC-RESIDENTIAL. NOTE: ELECTRICAL PLAN FOR THE FIRST |
| FLOOR SHOWS SMOKE AND ALARMS AND CARBON MONOXIDE ALARMS |
| COMBO, BUT SECOND FLOOR PLAN ONLY SHOWS SMOKE ALARMS. |
| |
| 7- SIZE OF FOOTINGS SHOWN ON SHEET S-1 DON'T MATCH |
| SIZES SHOWN ON THE WALL SECTIONS ON SHEET A-402. REVISE |
| AS REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 8- SPACING OF THE ANCHORS SHOWN ON THE LEDGER TABLE ON |
| SHEET S-2 AND S-3 DOESN'T MATCH SPACING SHOWN ON THE |
| TWO STORY WALL SECTION SHOWN ON SHEET A-402. REVISE AS |
| REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 9- SPECIFY ATTIC ACCESS LOCATION AND SIZE SHOWING |
| COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL. |
| |
| 10- BUILDING EXPOSURE SPECIFIED ON ROOF FRAMING NOTES |
| ON SHEETS S-2 AND S-3 DOESN'T MATCH THE EXPOSURE |
| SPECIFIED ON THE NEW CONSTRUCTION NOTES ON SHEET A-301. |
| REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 11- CLARIFY WHY THE DESIGN PRESSURES SHOWN ON SHEETS |
| S-2 AND S-3 ARE BASED ON 20 S.F TRIBUTARY AREA. PROVIDE |
| THE DESIGN PRESSURES BASED ON THE ACTUAL EFFECTIVE AREA |
| OR USE THE LOAD ASSOCIATED WITH THE LOWER EFFECTIVE |
| AREA. SEE NOTE "B" OF TABLE R301.2(2) FC-RESIDENTIAL. |
| NOTE: COORDINATE DESIGN PRESSURES WITH THOSE SHOWN ON |
| SHEET A-301. |
| CLARIFY WHY THE DESIGN PRESSURES FOR THE DOORS ARE |
| HIGHER THAN THE DESIGN PRESSURES FOR THE WINDOWS. |
| TYPICALLY, THE SMALLER THE OPENING THE HIGHER THE |
| DESIGN PRESSURES. |
| |
| 12- PROVIDE DETAILS AND SPECIFICATIONS FOR THE |
| CONNECTION AT TOP AND BOTTOM OF STEEL COLUMN LOCATED BY |
| THE GARAGE AREA AND GOING ALL THE WAY UP TO THE ROOF |
| FRAMING. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 13- SPECIFY DOUBLE LAYER OF WATER RESISTIVE BARRIER FOR |
| WOOD FRAMED WALL WITH STUCCO AS REQUIRED BY SEC. |
| R703.6.3 FBC-RESIDENTIAL. |
| |
| 14- REVISE STUCCO THICKNESS SPECIFIED ON ALL WALL |
| SECTIONS. NEED 7/8" MIN. THICKNESS NOT 5/8" AS REQUIRED |
| BY TABLE R702.1(1) FBC-RESIDENTIAL. |
| |
| 15- ENERGY CALCULATIONS SUBMITTED: |
| A) AREAS SHOWN ON ITEM #8 DON'T MATCH ARCHITECTURAL |
| PLANS SHEET A-101. REVISE AS REQUIRED. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). NOTE: CHECK FIRST FLOOR AREA AND SECOND FLOOR |
| AREA. |
| |
| B) FLOOR INFORMATION ON ITEM #8 IS MISSING THE |
| INSULATION R-VALUE BETWEEN THE GARAGE AND THE A/C AREA |
| ABOVE. REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| C) THE AREA SHOWN ON THE "SPACES" INFORMATION ON PAGE 2 |
| OF 5 DOESN'T MATCH PLANS. COORDINATE WITH ITEM #15(A) |
| ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| D) ROOF MATERIAL SHOWN ON PAGE 2 OF 5 DOESN'T MATCH |
| PLANS. REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| E) THE VENT RATIO SHOWN ON PAGE 2 OF 5 IS 1/300. |
| ARCHITECTURAL PLANS DON'T SPECIFY THIS VENT RATIO. |
| PERSON PREPARING THE ENERGY CALCULATIONS TO PROVIDE |
| COMPLETE DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE |
| WITH THE 1/300 RATIO AS REQUIRED BY THE EXCEPTION OF |
| SEC. R806.2 FBC-RESIDENTIAL. OR, SPECIFY THE TYPICAL |
| 1/150 VENT RATIO. |
| |
| F) CEILING AREAS SHOWN ON PAGE 3 OF 5 DON'T MATCH |
| PLANS. REVISE AS REQUIRED. WHERE ARE THESE AREAS TAKEN |
| FROM?. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| G) DOORS INFORMATION SHOWN ON PAGE 3 OF 5 DOESN'T MATCH |
| PLANS AND PRODUCT APPROVALS SUBMITTED. REVISE AS |
| REQUIRED. THE SIZE DOESN'T MATCH PLANS AND THIS IS A |
| DOOR WITH GLASS. DOORS WITH GLASS NEED TO BE CONSIDERED |
| IN THE GLAZING (WINDOWS) AREA AS REQUIRED BY SEC. |
| R405.5.3.3 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| H) WINDOWS INFORMATION SHOWN ON PAGE 3 OF 5 DOESN'T |
| MATCH PLANS. REVISE AS REQUIRED. NOTE: REVISE THE |
| ORIENTATION, AREA AND OVERHANG DEPTH AND SEPARATION TO |
| MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| I) GARAGE FLOOR AREA SHOWN ON PAGE 4 OF 5 DOESN'T MATCH |
| AREA SHOWN ON PLANS. REVISE AS REQUIRED. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| J) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| |
| NOTE: |
| LABEL FOR DOORS AND WINDOWS SHOWING THE U-FACTOR AND |
| SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL |
| BE REQUIRED WHEN THE ENERGY CALCULATIONS DON'T USE THE |
| DEFAULT FACTOR FOR GLAZING. |
| |
| 16- A) SOIL TEST REPORT SUBMITTED NEEDS THE ENGINEER'S |
| ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 |
| FLORIDA STATUTE WHEN SUBMITTING DOCUMENTS FOR PUBLIC |
| RECORDS. |
| |
| B) SOIL TEST REPORT SUBMITTED IS MISSING A PLOT PLAN |
| SHOWING THE LOCATION OF THE SOIL INVESTIGATION AS |
| REQUIRED BY SEC. 1803.6 FBC-BUILDING, 5TH EDITION |
| (2014). |
| |
| 17- PROVIDE COMPLETE WALL SECTIONS AND SPECIFICATIONS |
| FOR THE CONSTRUCTION OF THE CONCRETE BALCONIES AS SHOWN |
| ON PLANS. SEC. R301.1 FBC-RESIDENTIAL. NOTE: ALSO |
| SPECIFY FLOOR FINISH. THIS IS REQUIRED TO VERIFY |
| COMPLIANCE OF THE UNDERLAYMENT PRODUCT APPROVAL. |
| |
| 18- PROVIDE COMPLETE SECTION/DETAIL AND SPECIFICATIONS |
| FOR THE INSTALLATION OF THE DECORATIVE SHUTTERS SHOWN |
| ON THE FRONT ELEVATION ON THE SECOND FLOOR COVERED |
| BALCONY. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 19- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| A) ENTRY DOOR WITH SIDELITE AS SHOWN ON PLANS. NOTE: |
| NEED PRODUCT APPROVAL FOR DOOR THAT MEETS OR EXCEEDS |
| THE DESIGN PRESSURES CALCULATED BY THE ARCHITECT ON |
| SHEET A-301. AND NEED TO PROVIDE FLORIDA PRODUCT |
| APPROVAL COVER PAGE THAT CORRESPONDS TO DRAWING #: |
| ET0002 SUBMITTED. SUBMIT TWO COPIES. ONLY ONE WAS |
| SUBMITTED. |
| |
| B) MODIFIED BITUMEN FOR BALCONIES UNDERLAYMENT. NOA |
| 12-0703.06 SUBMITTED IS FOR WOOD DECKS. NEED PRODUCT |
| APPROVAL FOR CONCRETE DECK THAT IS DESIGNED TO RECEIVE |
| FINISH FLOOR AS SPECIFIED BY THE ARCHITECT OF RECORD. |
| NOTE: CLEARLY MARK SPECIFIC ASSEMBLY TO BE INSTALLED |
| AND PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF |
| THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES |
| FOR ALL DECK ZONES. |
| |
| C) PEEL AND STICK UNDERLAYMENT AS SPECIFIED ON |
| PLANS/DETAILS. ROOFING UNDERLAYMENT NOA 16-1116.09 |
| SUBMITTED: CLEARLY MARK WHICH APPROVED UNDERLAYMENT |
| ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE |
| WITH THE PROPOSED INSTALLATION. |
| |
| D) METAL ROOF AS SPECIFIED ON PLANS. |
| |
| E) ALUMINUM MULLIONS NOA 16-0218.03 SUBMITTED: CLEARLY |
| IDENTIFY SIZE OF MULLIONS AND WHERE IS GOING TO BE |
| INSTALLED. |
| |
| F) THERE ARE DIFFERENT NOA'S SUBMITTED FOR THE FRENCH |
| DOORS. NOA 16-0629.16 AND NOA 16-0629.17. CLEARLY MARK |
| WHERE EACH DOOR IS GOING TO BE INSTALLED TO VERIFY |
| COMPLIANCE WITH THE DESIGN PRESSURES. |
| |
| G) OVERHEAD GARAGE DOOR. NEED PRODUCT APPROVAL FOR DOOR |
| THAT MEETS THE DESIGN PRESSURES CALCULATED BY THE |
| ARCHITECT ON SHEET A-301. AND, PROVIDE COPY OF FLORIDA |
| PRODUCT APPROVAL COVER PAGE THAT CORRESPONDS TO |
| DRAWINGS SUBMITTED. |
| |
| H) GARAGE SIDE DOOR. NEED PRODUCT APPROVAL FOR DOOR |
| THAT MEETS THE DESIGN PRESSURES CALCULATED BY THE |
| ARCHITECT ON SHEET A-301. AND, PROVIDE COPY OF FLORIDA |
| PRODUCT APPROVAL COVER PAGE THAT CORRESPONDS TO |
| DRAWINGS SUBMITTED. |
| |
| I) BAHAMA SHUTTERS AS SPECIFIED ON PLANS. AND, PROVIDE |
| COMPLETE INSTALLATION SCHEDULE. SEE CITY SAMPLE. |
| |
| J) COLONIAL SHUTTERS AS SPECIFIED ON PLANS. AND, |
| PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY |
| SAMPLE. |
| |
| K) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| |
| L) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT |
| APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED |
| CONNECTOR. |
| |
| 20- ARCHITECT OF RECORD TO REVIEW AND APPROVE ALL |
| PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| AMENDMENTS. NOTE: PLEASE PLACE THE REVIEW STAMP ON THE |
| FRONT OF THE PRODUCT APPROVAL NOT ON THE BACK. THIS IS |
| REQUIRED FOR PROPER RECORD RETENTION PURPOSES. WHEN THE |
| STAMPS ARE PLACED ON THE BACK OF THE PRODUCT APPROVAL, |
| THEY DON'T GET SCANNED. SEC. 107.2.1.4 CITY AMENDMENTS. |
| |
| ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| FOR REFERENCE. |
| |