2017-11-22 13:42:42 | 2ND REVIEW FBC-2014 RESDIENTIAL MECHANICAL |
| PERMIT #17090693 |
| 11/1/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| THE 1ST REVIEW COMMENTS WERE NOT ADDRESSED AND STILL |
| EXIST. I HAVE REPRINTED THEM BELOW- PLEASE COMPLY. |
| |
| 1ST REVIEW FBC-2014 RESDIENTIAL MECHANICAL |
| PERMIT #17090693 |
| 11/1/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) TWO DIFFERENT SETS OF MECHANICAL PLANS BY TWO |
| DIFFERENT DESIGNERS HAVE BEEN SUBMITTED. THERE ARE THE |
| M-1 & M-2 PLANS IN THE MAIN PLANS SETS PREPARED BY THE |
| ARCHITECT OF RECORD, AND AN M.1 PLAN SEPARATE FROM THE |
| MAIN SETS PREPARED BY K.O. ENERGY DESIGN. PLEASE CHOOSE |
| ONE OF THE DESIGNS AND REMOVE THE OTHER. PLEASE NOTE |
| THAT THE ENERGY AND AC CALCULATIONS WERE PREPARED BY K. |
| O. ENERGY DESIGN, AND THE COMPLIANCE DATA LISTED FOR |
| THE AC SYSTEM DOES NOT MATCH THE SCHEDULE ON THE MAIN |
| SETS. |
| |
| 2) THE AIR BARRIER AND INSPECTION CHECKLIST IS NOT |
| ATTACHED WITH THE ENERGY COMPLIANCE FORM R405-2014. |
| PLEASE PROVIDE THE CHECKLIST. |
| |
| 3) FORM R405 IS MISSING THE OWNER/AGENT'S SIGNATURE AND |
| DATE. |
| |
| 4) THE AC LOAD CALCS ARE INDICATING THE FRONT DOOR |
| FACES SOUTH HOWEVER THE MAPS SHOW THE FRONT DOOR MUST |
| FACE NORTH. |
| |
| 5) THE 10KW HEATER SPECIFIED IN THE K.O. ENERGY |
| EQUIPMENT SCHEDULE IS UNDERSIZED FOR THE 48,948 |
| CALCULATED HEATING LOAD- MINIMUM 14KW REQUIRED |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |