Plan Review Notes
Plan Review Notes For Permit 17090693
Permit Number 17090693
Review Stop M
Sequence Number 2
Notes
Date Text
2017-11-22 13:42:422ND REVIEW FBC-2014 RESDIENTIAL MECHANICAL
 PERMIT #17090693
 11/1/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE 1ST REVIEW COMMENTS WERE NOT ADDRESSED AND STILL
 EXIST. I HAVE REPRINTED THEM BELOW- PLEASE COMPLY.
  
 1ST REVIEW FBC-2014 RESDIENTIAL MECHANICAL
 PERMIT #17090693
 11/1/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) TWO DIFFERENT SETS OF MECHANICAL PLANS BY TWO
 DIFFERENT DESIGNERS HAVE BEEN SUBMITTED. THERE ARE THE
 M-1 & M-2 PLANS IN THE MAIN PLANS SETS PREPARED BY THE
 ARCHITECT OF RECORD, AND AN M.1 PLAN SEPARATE FROM THE
 MAIN SETS PREPARED BY K.O. ENERGY DESIGN. PLEASE CHOOSE
 ONE OF THE DESIGNS AND REMOVE THE OTHER. PLEASE NOTE
 THAT THE ENERGY AND AC CALCULATIONS WERE PREPARED BY K.
 O. ENERGY DESIGN, AND THE COMPLIANCE DATA LISTED FOR
 THE AC SYSTEM DOES NOT MATCH THE SCHEDULE ON THE MAIN
 SETS.
  
 2) THE AIR BARRIER AND INSPECTION CHECKLIST IS NOT
 ATTACHED WITH THE ENERGY COMPLIANCE FORM R405-2014.
 PLEASE PROVIDE THE CHECKLIST.
  
 3) FORM R405 IS MISSING THE OWNER/AGENT'S SIGNATURE AND
 DATE.
  
 4) THE AC LOAD CALCS ARE INDICATING THE FRONT DOOR
 FACES SOUTH HOWEVER THE MAPS SHOW THE FRONT DOOR MUST
 FACE NORTH.
  
 5) THE 10KW HEATER SPECIFIED IN THE K.O. ENERGY
 EQUIPMENT SCHEDULE IS UNDERSIZED FOR THE 48,948
 CALCULATED HEATING LOAD- MINIMUM 14KW REQUIRED
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  