Plan Review Notes For Permit 17090693 |
Permit Number |
17090693 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-11-01 10:00:24 | 1ST REVIEW FBC-2014 RESDIENTIAL MECHANICAL | | PERMIT #17090693 | | 11/1/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) TWO DIFFERENT SETS OF MECHANICAL PLANS BY TWO | | DIFFERENT DESIGNERS HAVE BEEN SUBMITTED. THERE ARE THE | | M-1 & M-2 PLANS IN THE MAIN PLANS SETS PREPARED BY THE | | ARCHITECT OF RECORD, AND AN M.1 PLAN SEPARATE FROM THE | | MAIN SETS PREPARED BY K.O. ENERGY DESIGN. PLEASE CHOOSE | | ONE OF THE DESIGNS AND REMOVE THE OTHER. PLEASE NOTE | | THAT THE ENERGY AND AC CALCULATIONS WERE PREPARED BY K. | | O. ENERGY DESIGN, AND THE COMPLIANCE DATA LISTED FOR | | THE AC SYSTEM DOES NOT MATCH THE SCHEDULE ON THE MAIN | | SETS. | | | | 2) THE AIR BARRIER AND INSPECTION CHECKLIST IS NOT | | ATTACHED WITH THE ENERGY COMPLIANCE FORM R405-2014. | | PLEASE PROVIDE THE CHECKLIST. | | | | 3) FORM R405 IS MISSING THE OWNER/AGENT'S SIGNATURE AND | | DATE. | | | | 4) THE AC LOAD CALCS ARE INDICATING THE FRONT DOOR | | FACES SOUTH HOWEVER THE MAPS SHOW THE FRONT DOOR MUST | | FACE NORTH. | | | | 5) THE 10KW HEATER SPECIFIED IN THE K.O. ENERGY | | EQUIPMENT SCHEDULE IS UNDERSIZED FOR THE 48,948 | | CALCULATED HEATING LOAD- MINIMUM 14KW REQUIRED | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|