2017-10-03 11:53:25THIS PLAN HAS BEEN PASSED PROVISIONALLY.
  
 PLAN HAS BEEN MARKED ACCORDINGLY.
  
 1. ALL OUTDOOR GFCI RECEPTACLES WILL BE OF THE WP TYPE
 NEC 406.9(B1)
  
 2. OUTDOOR LUMINAIRES WILL BE SUITABLE FOR USE IN WET
 LOCATION. IF LUMINAIRE IS A HIGH HAT "CAN" TYPE IT WILL
 HAVE A VP TRIM. NEC 410.10
  
 3. GARAGE DOOR OPENER RECEPTACLES REQUIRE GFCI
 PROTECTION. NEC 210.8 (A2)
  
 4. CIRCUIT A-18 FOR SMALL APPLIANCE WILL NOT SERVE D/W
 OR DISPOSAL. NEC 210.52(B2)
  
 5. FBC-R M1305.1.3.2 AIR-HANDLING UNITS.
 AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE
 FOLLOWING CONDITIONS ARE MET:
 (1)THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
  
 6. BOND GAS AND C/W PIPE IF APPLICABLE. NEC 250.104
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE