Plan Review Notes For Permit 17090693 |
Permit Number |
17090693 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-10-03 11:53:25 | THIS PLAN HAS BEEN PASSED PROVISIONALLY. | | | | PLAN HAS BEEN MARKED ACCORDINGLY. | | | | 1. ALL OUTDOOR GFCI RECEPTACLES WILL BE OF THE WP TYPE | | NEC 406.9(B1) | | | | 2. OUTDOOR LUMINAIRES WILL BE SUITABLE FOR USE IN WET | | LOCATION. IF LUMINAIRE IS A HIGH HAT "CAN" TYPE IT WILL | | HAVE A VP TRIM. NEC 410.10 | | | | 3. GARAGE DOOR OPENER RECEPTACLES REQUIRE GFCI | | PROTECTION. NEC 210.8 (A2) | | | | 4. CIRCUIT A-18 FOR SMALL APPLIANCE WILL NOT SERVE D/W | | OR DISPOSAL. NEC 210.52(B2) | | | | 5. FBC-R M1305.1.3.2 AIR-HANDLING UNITS. | | AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE | | FOLLOWING CONDITIONS ARE MET: | | (1)THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN | | 6 FEET (1829 MM) OF AN ATTIC ACCESS. | | | | 6. BOND GAS AND C/W PIPE IF APPLICABLE. NEC 250.104 | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | 5TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | PART VIII ELECTRICAL | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | FRANK GIAQUINTO | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WPB | | DEVELOPMENT SERVICES DEPT. | | CELL 561-657-1653 | | [email protected] | | | | |
|