2017-10-26 15:12:08 | BUILDING PLAN REVIEW |
| 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PER FOUNDATION NOTE ON PAGE S-0, PROVIDE A SIGNED |
| AND SEALED GEOTECHNICAL REPORT. THE REPORT SHALL BE |
| ISSUED BY AN ACCREDITED LABORATORY. |
| 2. OWNER/AGENT TO SIGN ENERGY SUBMITTAL. |
| 3. DETAIL 3, PAGE A-5 SPECIFIES 1X2 WOOD FURRING ON |
| INTERIOR WALLS. TYPICAL DOOR AND WINDOW SILL DETAILS ON |
| PAGE A-6 SPECIFIES 15/8 METAL FURRING. PLEASE CLARIFY. |
| 4. PLEASE PROVIDE AN INTERPRETATION FOR THE |
| INSTALLATION OF SHERWIN WILLIAMS SHER-CRETE FLEXIBLE |
| CONCRETE WATER PROOFING AT ALL DOOR AND WINDOW MASONRY |
| OPENINGS. IS THIS A QA/QC MEASURE OR A CODE |
| REQUIREMENT? PLEASE CLARIFY. |
| 5. TYPICAL DOOR BUCK DETAIL ON PAGE A-6 SPECIFIES 2X |
| P.T. WOOD BUCKS TO BE ATTACHED PER PRODUCT APPROVALS. |
| PRODUCT APPROVALS SPECIFIES WOOD BUCK DESIGN AND |
| INSTALLATION IS THE RESPONSIBILITY OF THE EOR AND AOR. |
| PROVIDE ATTACHMENT DETAIL FOR 2X WOOD BUCKS AT EXT. |
| DOORS. |
| 6. NOTICE - MANDATORY RESIDENTIAL AIR INFILTRATION |
| (BLOWER DOOR) TEST REQUIRED. |
| 7. TYPICAL WINDOW ANCHORAGE DETAIL, PAGE A-6 REQUIRES A |
| MIN. OF R-7.0 FOIL INSULATION. ENERGY SUBMITTAL |
| REQUIRES A MIN. OF R-4.2. PLEASE CLARIFY. |
| 8. PROVIDE CERTIFICATE OF TERMITE TREATMENT PER FBC, |
| SETION 1816. |
| 9. REFERENCE CONCRETE BEAM AND MASONRY LINTEL SCHEDULE, |
| PAGE S-1. IDENTIFY WHAT A MB-3 IS FOR AN 8" WALL? |
| 10. REFERENCE CONCRETE COLUMN SCHEDULE, PAGE S-1. THE |
| DESCRIPTION FOR TWO DIFFERENT FILLED CELL REINFORCEMENT |
| REQUIREMENTS APPEARS TO BE THE SAME. PLEASE CLARIFY. |
| 11. THE VERTICAL REINFORCEMENT SPACING FOR A MW-1 TYPE |
| WALL, SEE MASONRY WALL SCHEDULE, PAGE S-1, DOES NOT |
| CORRESPOND TO THE VERTICAL SPACING ON THE FOUNDATION |
| PLAN. PLEASE CLARIFY. |
| 12. REFERENCE SOIL STATEMENT, PAGE S-1. PLEASE CLARIFY |
| WHAT THE STATEMENT "WITH THE SO S PREPERATION, ETC." |
| MEANS IN ITEM B. |
| 13. PROVIDE SHOP DRAWINGS FOR PROPOSED STAIRS. THESE |
| MAY BE LISTED AS A DEFFERRED SUBMITTAL. SHOP DRAWINGS |
| MUST BE REVIEWED AND APPROVED PRIOR TO INSTALLATION. |
| 14. ROOF SHEATHING FASTENER DETAIL 2, PAGE A-5 IS IN |
| CONFLICT WITH ROOF SHEATHING FASTENER SCHEDULE, PAGE |
| S-2. PLEASE CLARIFY. |
| 15. REFERENCE DETAIL D, PAGE S-6. THERE ARE TWO |
| DIFFERENT SHEATING PRODUCTS LISTED FOR THE SAME |
| INSTALLATION. BOTH PRODUCTS ARE IN CONFLICT WITH THE |
| SHEATHING DETAIL ON PAGE A-5. PLEASE CLARIFY. |
| 16. REFERENCE DETAIL H, PAGE S-7. HORIZONTAL |
| REINFORCEMENT (DUROWALL) REQUIRED FOR MASONRY WALLS PER |
| FBCR 606.12.2.2.3. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED AND MARK VOID. |
| |
| |
| |