Plan Review Notes
Plan Review Notes For Permit 17090693
Permit Number 17090693
Review Stop B
Sequence Number 1
Notes
Date Text
2017-10-26 15:12:08BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PER FOUNDATION NOTE ON PAGE S-0, PROVIDE A SIGNED
 AND SEALED GEOTECHNICAL REPORT. THE REPORT SHALL BE
 ISSUED BY AN ACCREDITED LABORATORY.
 2. OWNER/AGENT TO SIGN ENERGY SUBMITTAL.
 3. DETAIL 3, PAGE A-5 SPECIFIES 1X2 WOOD FURRING ON
 INTERIOR WALLS. TYPICAL DOOR AND WINDOW SILL DETAILS ON
 PAGE A-6 SPECIFIES 15/8 METAL FURRING. PLEASE CLARIFY.
 4. PLEASE PROVIDE AN INTERPRETATION FOR THE
 INSTALLATION OF SHERWIN WILLIAMS SHER-CRETE FLEXIBLE
 CONCRETE WATER PROOFING AT ALL DOOR AND WINDOW MASONRY
 OPENINGS. IS THIS A QA/QC MEASURE OR A CODE
 REQUIREMENT? PLEASE CLARIFY.
 5. TYPICAL DOOR BUCK DETAIL ON PAGE A-6 SPECIFIES 2X
 P.T. WOOD BUCKS TO BE ATTACHED PER PRODUCT APPROVALS.
 PRODUCT APPROVALS SPECIFIES WOOD BUCK DESIGN AND
 INSTALLATION IS THE RESPONSIBILITY OF THE EOR AND AOR.
 PROVIDE ATTACHMENT DETAIL FOR 2X WOOD BUCKS AT EXT.
 DOORS.
 6. NOTICE - MANDATORY RESIDENTIAL AIR INFILTRATION
 (BLOWER DOOR) TEST REQUIRED.
 7. TYPICAL WINDOW ANCHORAGE DETAIL, PAGE A-6 REQUIRES A
 MIN. OF R-7.0 FOIL INSULATION. ENERGY SUBMITTAL
 REQUIRES A MIN. OF R-4.2. PLEASE CLARIFY.
 8. PROVIDE CERTIFICATE OF TERMITE TREATMENT PER FBC,
 SETION 1816.
 9. REFERENCE CONCRETE BEAM AND MASONRY LINTEL SCHEDULE,
 PAGE S-1. IDENTIFY WHAT A MB-3 IS FOR AN 8" WALL?
 10. REFERENCE CONCRETE COLUMN SCHEDULE, PAGE S-1. THE
 DESCRIPTION FOR TWO DIFFERENT FILLED CELL REINFORCEMENT
 REQUIREMENTS APPEARS TO BE THE SAME. PLEASE CLARIFY.
 11. THE VERTICAL REINFORCEMENT SPACING FOR A MW-1 TYPE
 WALL, SEE MASONRY WALL SCHEDULE, PAGE S-1, DOES NOT
 CORRESPOND TO THE VERTICAL SPACING ON THE FOUNDATION
 PLAN. PLEASE CLARIFY.
 12. REFERENCE SOIL STATEMENT, PAGE S-1. PLEASE CLARIFY
 WHAT THE STATEMENT "WITH THE SO S PREPERATION, ETC."
 MEANS IN ITEM B.
 13. PROVIDE SHOP DRAWINGS FOR PROPOSED STAIRS. THESE
 MAY BE LISTED AS A DEFFERRED SUBMITTAL. SHOP DRAWINGS
 MUST BE REVIEWED AND APPROVED PRIOR TO INSTALLATION.
 14. ROOF SHEATHING FASTENER DETAIL 2, PAGE A-5 IS IN
 CONFLICT WITH ROOF SHEATHING FASTENER SCHEDULE, PAGE
 S-2. PLEASE CLARIFY.
 15. REFERENCE DETAIL D, PAGE S-6. THERE ARE TWO
 DIFFERENT SHEATING PRODUCTS LISTED FOR THE SAME
 INSTALLATION. BOTH PRODUCTS ARE IN CONFLICT WITH THE
 SHEATHING DETAIL ON PAGE A-5. PLEASE CLARIFY.
 16. REFERENCE DETAIL H, PAGE S-7. HORIZONTAL
 REINFORCEMENT (DUROWALL) REQUIRED FOR MASONRY WALLS PER
 FBCR 606.12.2.2.3.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  