Plan Review Notes
Plan Review Notes For Permit 17090538
Permit Number 17090538
Review Stop M
Sequence Number 1
Notes
Date Text
2017-10-03 12:14:521ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 REVISION #17090538
 MASTER #17070265
 10/3/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER