2017-11-03 15:18:472ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17090496
 11/3/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) DISCREPTANCIES IN THE PLANS AND SUBMITTALS:
  
 A) SHEET AC-1: THE AAON MODEL NUMBER RNA SHOWN IN THE
 SCHEDULE DOESN'T MATCH THE MODEL NUMBER RN ON THE AHRI
 CERTIFICATE.
  
 B) AC-1: THE SCHEDULE SHOWS EER- 14.2, THE AHRI SHOWS
 EER- 12.70.
  
 C) AC-1: THE SCHEDULE SHOWS TOTAL MBH- 133.02, THE AHRI
 SHOWS 128.
  
 D) AC-1: THE SCHEDULE SHOWS TOTAL CFMS- 1600, THE AAON
 MANUFACTURER'S SPECIFICATIONS SHOW MODEL RN-011 TOTAL
 CFMS- 3600.
  
 E) AC-1: THE RTU DETAIL SHOWS A 24" HIGH CURB, THE FL.
 PRODUCT APPROVAL FOR THE AAON CURB SHOWS MAX HEIGHT- 1'
 2".
  
 F) AC-1: THE RTU DETAILS SHOWS ATTACHMENT OF THE UNIT
 TO THE CURB USING STEEL STRAPS ON THE FACES OF THE UNTI
 AND CURB, THE PRODUCT APPROVAL SHOWS STEEL CLIPS THAT
 WRAP AROUND THE BACKSIDE OF THE CURB.
  
 G) AC-1: THE RTU DETAIL SHOWS ATTACHMENT OF THE CURB TO
 A CONCRETE STRUCTURE, HOWEVER THE PRODUCT APPROVAL
 SHOWS ONLY AN ATTACHMENT TO STEEL STRUCTUURE AND DOES
 NOT SHOW AN ATTACHMENT DETAIL FOR CONCRETE.
  