2017-09-28 11:02:551ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17090496
 9/28/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 11-TON SYSTEM- SECTION R403.6.1 C403.2.1 FBC-14 ENERGY
 CONSERVATION & SECTION 312.1 FBC-14 MECHANICAL.
  
 2) THE ENGINEERING FOR TIE DOWN OF THE NEW OAU IS
 INCOMPLETE. THE SUBMITTAL FROM ROBERT W. LAFFERTY PE
 DOES NOT PROVIDE ANY ANCHORING OR FASTENING INFORMATION
 AND THE DETAILS ON SHEET AC-1 ARE INCOMPLETE. INDICATE
 ON THE SUBMITTAL AND PLANS THE TYPE, SIZE AND GAUGE OF
 STEEL STRAPPING, AND NUMBER OF STRAPS REQUIRED TO TIE
 THE RTU TO THE CURB. SUBMIT THE NOA FOR THE CURB WITH
 APPROVAL STAMP BY THE ENGINEER OF RECORD.
  
 3) THE EOR ROBERT W. LAFFERTY MUST PROVIDE A TITLE
 BLOCK ON THE PLAN SHEETS AND THE TIE-DOWN SUBMITTAL-
 SECTION G15-23.002 FAC.
  