Plan Review Notes For Permit 17090495 |
Permit Number |
17090495 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-09-28 15:28:45 | 9/28/17 1ST REVIEW PLUMBING | | | | 1) PER LINE #5 OF JOB PROPOSAL IT LIST THAT PVC WILL BE | | PUSH THROUGH THE BLOCK WALL AND A NEW PVC BALL VALVE | | WOULD THEN BE INSTALLED ON THE INSIDE WALL. MAIN VALVE | | MUST BE LOCATED OUTSIDE OF THE STRUCTURE AND MATERIAL | | USE OF PVC UP TO THAT VALVE IS APPROVED FOR OUTSIDE USE | | ONLY PER FPC 605.3. ANY MATERIAL USED AFTER THE FULL | | OPEN MAIN VALVE MUST COMPLY WITH TABLE 605.4 AS IT | | WOULD BE CONSIDERED AS WATER DISTRIBUTION PIPING. | | | | 2) THERE IS CURRENTLY AN UNPERMITTED BACKFLOW AT THIS | | SITE THAT WAS CITED ON 8/16/17. THIS MATTER MUST BE | | RESOLVED BEFORE ANY OTHER PLUMBING PERMITS ARE ISSUED. | | | | TIM HUNT | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | 561-805-6695 | | [email protected] | | |
|