2018-01-29 14:10:0401/29/18
 RECEIVED REVISED CALCULATIONS FROM NICOLE BLACKWELL
 FROM QUICKCALCS.
 (ENERGY CALCULATIONS AND EQUIPMENT SIZING
 CALCULATIONS). JG.
  
  
  
 EQUIPMENT SIZING CALCULATIONS REVISION COURTESY REVIEW:
 1- THE NUMBER OF PEOPLE SHOWN ON THE EQUIPMENT SIZING
 CALCULATIONS DOESN'T MATCH THE NUMBER OF PEOPLE SHOWN
 ON THE ENERGY CALCULATIONS. REVISE AS REQUIRED.
  
 NEW COMMENT:
 1- NUMBER OF PEOPLE SHOWN ON THE ENERGY CALCULATIONS
 WAS CHANGED FROM 8 PEOPLE TO 12 PEOPLE. 8 PEOPLE WAS A
 REASONABLE NUMBER OF PEOPLE FOR A 6 BEDROOM HOUSE WITH
 2 MASTER BEDROOMS. THAT'S WHY I DIDN'T SAY ANYTHING
 ABOUT THE NUMBER OF PEOPLE CONSIDERED ON THE ENERGY
 CALCULATIONS. REVISED ENERGY CALCULATIONS ARE NOW
 SHOWING 4 PEOPLE IN THE GREAT ROOM. THIS DOESN'T LOOK
 CORRECT SINCE THE NUMBER OF PEOPLE ARE ALREADY COUNTED
 IN THE BEDROOMS. REVISE AS REQUIRED. NOTE: NUMBER OF
 PEOPLE MAY AFFECT THE SIZING OF THE A/C EQUIPMENT. MAY
 BE THAT'S WHY THE EQUIPMENT SIZING CALCULATIONS ARE
 USING 12 PEOPLE INSTEAD OF 8. THE ENERGY CODE DOESN'T
 ALLOW TO USE FACTORS THAT AFFECT THE EQUIPMENT SIZING.
 SEE SEC. R403.6.1 FBC-ENERGY CONSERVATION. REVISE AS
 REQUIRED USING THE CORRECT NUMBER OF PEOPLE.
  
 2- REVISE A/C PLAN TO REFLECT THE NEW EQUIPMENT.
 NOTE: DON'T FORGET TO HAVE THE NAME AND SIGNATURE OF
 THE A/C CONTRACTOR RESPONSIBLE FOR THE A/C DESIGN.