Plan Review Notes
Plan Review Notes For Permit 17090467
Permit Number 17090467
Review Stop B
Sequence Number 6
Notes
Date Text
2018-01-29 13:36:5101/29/18
 RECEIVED REVISED CALCULATIONS FROM NICOLE BLACKWELL
 FROM QUICKCALCS.
 (ENERGY CALCULATIONS AND EQUIPMENT SIZING
 CALCULATIONS). JG.
  
  
 ENERGY CALCULATIONS REVISION COURTESY REVIEW;
 1- THE PERMIT OFFICE IS CITY OF WEST PALM BEACH NOT
 CITY OF PALM BEACH. (PALM BEACH IS ANOTHER
 MUNICIPALITY)
 2- OWNER OR LEGAL AGENT TO SIGN AND DATE ENERGY
 CALCULATIONS.
 3- BUILDER TO COMPLETE THE EPL CARD.
  
 NEW COMMENT:
 1- NUMBER OF PEOPLE WAS CHANGED FROM 8 PEOPLE TO 12
 PEOPLE. 8 PEOPLE WAS A REASONABLE NUMBER OF PEOPLE FOR
 A 6 BEDROOM HOUSE WITH 2 MASTER BEDROOMS. THAT'S WHY I
 DIDN'T SAY ANYTHING ABOUT THE NUMBER OF PEOPLE
 CONSIDERED ON THE ENERGY CALCULATIONS. REVISED ENERGY
 CALCULATIONS ARE NOW SHOWING 4 PEOPLE IN THE GREAT
 ROOM. THIS DOESN'T LOOK CORRECT SINCE THE NUMBER OF
 PEOPLE ARE ALREADY COUNTED IN THE BEDROOMS. REVISE AS
 REQUIRED. NOTE: NUMBER OF PEOPLE MAY AFFECT THE SIZING
 OF THE A/C EQUIPMENT. MAY BE THAT'S WHY THE EQUIPMENT
 SIZING CALCULATIONS ARE USING 12 PEOPLE INSTEAD OF 8.
 THE ENERGY CODE DOESN'T ALLOW TO USE FACTORS THAT
 AFFECT THE EQUIPMENT SIZING. SEE SEC. R403.6.1
 FBC-ENERGY CONSERVATION. REVISE AS REQUIRED USING THE
 CORRECT NUMBER OF PEOPLE. EQUIPMENT SIZING CALCULATIONS
 WILL NEED TO BE REVISED AS WELL.