Plan Review Notes For Permit 17090467 |
Permit Number |
17090467 |
|
Review Stop |
B |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2018-01-29 13:36:51 | 01/29/18 | | RECEIVED REVISED CALCULATIONS FROM NICOLE BLACKWELL | | FROM QUICKCALCS. | | (ENERGY CALCULATIONS AND EQUIPMENT SIZING | | CALCULATIONS). JG. | | | | | | ENERGY CALCULATIONS REVISION COURTESY REVIEW; | | 1- THE PERMIT OFFICE IS CITY OF WEST PALM BEACH NOT | | CITY OF PALM BEACH. (PALM BEACH IS ANOTHER | | MUNICIPALITY) | | 2- OWNER OR LEGAL AGENT TO SIGN AND DATE ENERGY | | CALCULATIONS. | | 3- BUILDER TO COMPLETE THE EPL CARD. | | | | NEW COMMENT: | | 1- NUMBER OF PEOPLE WAS CHANGED FROM 8 PEOPLE TO 12 | | PEOPLE. 8 PEOPLE WAS A REASONABLE NUMBER OF PEOPLE FOR | | A 6 BEDROOM HOUSE WITH 2 MASTER BEDROOMS. THAT'S WHY I | | DIDN'T SAY ANYTHING ABOUT THE NUMBER OF PEOPLE | | CONSIDERED ON THE ENERGY CALCULATIONS. REVISED ENERGY | | CALCULATIONS ARE NOW SHOWING 4 PEOPLE IN THE GREAT | | ROOM. THIS DOESN'T LOOK CORRECT SINCE THE NUMBER OF | | PEOPLE ARE ALREADY COUNTED IN THE BEDROOMS. REVISE AS | | REQUIRED. NOTE: NUMBER OF PEOPLE MAY AFFECT THE SIZING | | OF THE A/C EQUIPMENT. MAY BE THAT'S WHY THE EQUIPMENT | | SIZING CALCULATIONS ARE USING 12 PEOPLE INSTEAD OF 8. | | THE ENERGY CODE DOESN'T ALLOW TO USE FACTORS THAT | | AFFECT THE EQUIPMENT SIZING. SEE SEC. R403.6.1 | | FBC-ENERGY CONSERVATION. REVISE AS REQUIRED USING THE | | CORRECT NUMBER OF PEOPLE. EQUIPMENT SIZING CALCULATIONS | | WILL NEED TO BE REVISED AS WELL. |
|