2018-01-26 14:40:47 | RECEIVED E-MAIL FROM NICOLE BLACKWELL FROM QUICKCALCS. |
| NEW ENERGY CALCULATIONS AND EQUIPMENT SIZING |
| CALCULATIONS. JG. |
| |
| |
| ENERGY CALCULATIONS COURTESY REVIEW; |
| 1- CORRECT ADDRESS IS 5401 S. OLIVE AVE NOT 541. |
| 2- NEED BUILDER'S NAME. |
| 3- THE PERMIT OFFICE IS CITY OF WEST PALM BEACH NOT |
| PALM BEACH COUNTY |
| 4- NEED THE NAME OF THE PERSON PREPARING THE ENERGY |
| CALCULATIONS AS REQUIRED BY SEC. R405.4.2 FBC ENERGY |
| CONSERVATION. |
| 5- ITEM #15 IS TAKING THE CEILING FAN CREDIT. PLANS |
| DON'T SHOW CEILING FANS. IF FANS ARE REQUIRED TO PASS |
| THE ENERGY CALCULATIONS, THEN ENGINEER OF RECORD NEEDS |
| TO REVISE PLAN SHOWING THE CEILING FAN LOCATION AND |
| SIZE AS REQUIRED BY TABLE R405.7.6 FBC ENERGY |
| CONSERVATION. NOTE: GREAT ROOM WILL NEED TO HAVE 2 |
| CEILING FANS. |
| 6- OWNER OR LEGAL AGENT TO SIGN AND DATE ENERGY |
| CALCULATIONS. |
| 7- SPACES INFORMATION ON PAGE 2 OF 7. CLARIFY WHY ITEM |
| #9 IS THE KITCHEN, BUT IN THE KITCHEN COLUMN IT SAYS |
| THAT THERE IS NOT KITCHEN? |
| 8- ATTIC VENTILATION ON PAGE 3 OF 7 SPECIFIES A VENT |
| RATIO OF 1/300. PLANS DON'T PROVIDE ANY INFORMATION |
| SHOWING THAT THE HOUSE WAS DESIGNED WITH A VENT RATIO |
| OF 1/300. TYPICALLY THE VENT RATIO IS 1/150. IF USING |
| THE 1/300 VENT RATIO, THEN ENGINEER OF RECORD NEEDS TO |
| REVISE PLANS. SEE THE EXCEPTION ON SEC. R806.2 FBC |
| RESIDENTIAL FOR REQUIREMENTS OF A 1/300 VENT RATIO. |
| 9- THE WALL AND WINDOW INFORMATION ON PAGE 5 OF 7 NEEDS |
| TO BE REVISED TO SHOW THE ACTUAL ORIENTATION OF THE |
| BUILDING. FOR EXAMPLE THE ENTRY DOORS ARE FACING EAST |
| NOT WEST. AND, THE COVERED PATIO SLIDING GLASS DOORS |
| ARE FACING WEST NOT EAST. REVISE AS REQUIRED. |
| 10- BUILDER TO COMPLETE THE EPL CARD. |