Notes
Date Text
2018-01-26 14:40:47RECEIVED E-MAIL FROM NICOLE BLACKWELL FROM QUICKCALCS.
 NEW ENERGY CALCULATIONS AND EQUIPMENT SIZING
 CALCULATIONS. JG.
  
  
 ENERGY CALCULATIONS COURTESY REVIEW;
 1- CORRECT ADDRESS IS 5401 S. OLIVE AVE NOT 541.
 2- NEED BUILDER'S NAME.
 3- THE PERMIT OFFICE IS CITY OF WEST PALM BEACH NOT
 PALM BEACH COUNTY
 4- NEED THE NAME OF THE PERSON PREPARING THE ENERGY
 CALCULATIONS AS REQUIRED BY SEC. R405.4.2 FBC ENERGY
 CONSERVATION.
 5- ITEM #15 IS TAKING THE CEILING FAN CREDIT. PLANS
 DON'T SHOW CEILING FANS. IF FANS ARE REQUIRED TO PASS
 THE ENERGY CALCULATIONS, THEN ENGINEER OF RECORD NEEDS
 TO REVISE PLAN SHOWING THE CEILING FAN LOCATION AND
 SIZE AS REQUIRED BY TABLE R405.7.6 FBC ENERGY
 CONSERVATION. NOTE: GREAT ROOM WILL NEED TO HAVE 2
 CEILING FANS.
 6- OWNER OR LEGAL AGENT TO SIGN AND DATE ENERGY
 CALCULATIONS.
 7- SPACES INFORMATION ON PAGE 2 OF 7. CLARIFY WHY ITEM
 #9 IS THE KITCHEN, BUT IN THE KITCHEN COLUMN IT SAYS
 THAT THERE IS NOT KITCHEN?
 8- ATTIC VENTILATION ON PAGE 3 OF 7 SPECIFIES A VENT
 RATIO OF 1/300. PLANS DON'T PROVIDE ANY INFORMATION
 SHOWING THAT THE HOUSE WAS DESIGNED WITH A VENT RATIO
 OF 1/300. TYPICALLY THE VENT RATIO IS 1/150. IF USING
 THE 1/300 VENT RATIO, THEN ENGINEER OF RECORD NEEDS TO
 REVISE PLANS. SEE THE EXCEPTION ON SEC. R806.2 FBC
 RESIDENTIAL FOR REQUIREMENTS OF A 1/300 VENT RATIO.
 9- THE WALL AND WINDOW INFORMATION ON PAGE 5 OF 7 NEEDS
 TO BE REVISED TO SHOW THE ACTUAL ORIENTATION OF THE
 BUILDING. FOR EXAMPLE THE ENTRY DOORS ARE FACING EAST
 NOT WEST. AND, THE COVERED PATIO SLIDING GLASS DOORS
 ARE FACING WEST NOT EAST. REVISE AS REQUIRED.
 10- BUILDER TO COMPLETE THE EPL CARD.