2018-01-17 11:52:46RESIDENTIAL (R3) REVISION FOURTH MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE: REVISION FEES APPLY ON EVERY RE-SUBMITTAL.
  
  
 ORIGINAL COMMENT:
 1- A/C EQUIPMENT SIZING CALCULATIONS SUBMITTED: PROVIDE
 COMPLETE EQUIPMENT SIZING CALCULATIONS "BASED ON
 BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF THE
 BUILDING" AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED. ONLY THE
 SUMMARY PAGES WERE SUBMITTED. NEED THE COMPLETE
 EQUIPMENT SIZING CALCULATIONS WORKSHEETS.
  
  
 RESPONSE:
 SAME SUMMARY CALCULATIONS WERE RE-SUBMITTED AGAIN. NEED
 TO PROVIDE COMPLETE WORKSHEETS TO VERIFY HOW THE
 EQUIPMENT WAS SIZED.
 THIS WAS REQUIRED FROM THE BEGINNING OF THE MECHANICAL
 REVIEWS BECAUSE IT LOOKS LIKE THE ORIGINAL CALCULATIONS
 WERE DONE BASED ON THE BUILDING ORIENTATION WORST CASE
 SCENARIO. BY DOING THIS THE EQUIPMENT MAY BE
 OVER-SIZED. SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014) REQUIRES CALCULATIONS TO BE DONE ON THE
 ACTUAL ORIENTATION OF THE BUILDING AND DOESN'T ALLOW
 EQUIPMENT OVERSIZING. BASED ON THE CALCULATIONS
 SUBMITTED, THE TOTAL COOLING LOAD IS 32924. SEC.
 R403.6.1.1 ALLOWS NOT MORE THAN 1.15 TIMES EQUIPMENT
 SIZING GREATER THAN THE CALCULATED LOAD. THEREFORE, THE
 EQUIPMENT SIZE SHOULD BE 3 TON. NOT 3.5 TON AS SHOWN ON
 LOAD CALCULATIONS SUBMITTED. THIS ISSUE WAS NOT
 VERIFIED BEFORE, BECAUSE THE ORIGINAL REQUEST TO
 PROVIDE COMPLETE REPORT WAS NEVER ADDRESSED.
  
  
  