2018-01-17 11:52:46 | RESIDENTIAL (R3) REVISION FOURTH MECHANICAL REVIEW |
| CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| NOTE: REVISION FEES APPLY ON EVERY RE-SUBMITTAL. |
| |
| |
| ORIGINAL COMMENT: |
| 1- A/C EQUIPMENT SIZING CALCULATIONS SUBMITTED: PROVIDE |
| COMPLETE EQUIPMENT SIZING CALCULATIONS "BASED ON |
| BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF THE |
| BUILDING" AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| RESPONSE: REPEAT COMMENT. NOT ADDRESSED. ONLY THE |
| SUMMARY PAGES WERE SUBMITTED. NEED THE COMPLETE |
| EQUIPMENT SIZING CALCULATIONS WORKSHEETS. |
| |
| |
| RESPONSE: |
| SAME SUMMARY CALCULATIONS WERE RE-SUBMITTED AGAIN. NEED |
| TO PROVIDE COMPLETE WORKSHEETS TO VERIFY HOW THE |
| EQUIPMENT WAS SIZED. |
| THIS WAS REQUIRED FROM THE BEGINNING OF THE MECHANICAL |
| REVIEWS BECAUSE IT LOOKS LIKE THE ORIGINAL CALCULATIONS |
| WERE DONE BASED ON THE BUILDING ORIENTATION WORST CASE |
| SCENARIO. BY DOING THIS THE EQUIPMENT MAY BE |
| OVER-SIZED. SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH |
| EDITION (2014) REQUIRES CALCULATIONS TO BE DONE ON THE |
| ACTUAL ORIENTATION OF THE BUILDING AND DOESN'T ALLOW |
| EQUIPMENT OVERSIZING. BASED ON THE CALCULATIONS |
| SUBMITTED, THE TOTAL COOLING LOAD IS 32924. SEC. |
| R403.6.1.1 ALLOWS NOT MORE THAN 1.15 TIMES EQUIPMENT |
| SIZING GREATER THAN THE CALCULATED LOAD. THEREFORE, THE |
| EQUIPMENT SIZE SHOULD BE 3 TON. NOT 3.5 TON AS SHOWN ON |
| LOAD CALCULATIONS SUBMITTED. THIS ISSUE WAS NOT |
| VERIFIED BEFORE, BECAUSE THE ORIGINAL REQUEST TO |
| PROVIDE COMPLETE REPORT WAS NEVER ADDRESSED. |
| |
| |
| |