Plan Review Notes For Permit 17090467 |
Permit Number |
17090467 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2017-12-27 15:45:42 | RESIDENTIAL (R3) REVISION THIRD MECHANICAL REVIEW | | CHECKLIST. | | CODE: FBC 5TH EDITION (2014). | | | | NOTE: REVISION FEES APPLY ON EVERY RE-SUBMITTAL. | | | | | | 1- A/C EQUIPMENT SIZING CALCULATIONS SUBMITTED: PROVIDE | | COMPLETE EQUIPMENT SIZING CALCULATIONS "BASED ON | | BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF THE | | BUILDING" AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY | | CONSERVATION, 5TH EDITION (2014). | | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. ONLY THE | | SUMMARY PAGES WERE SUBMITTED. NEED THE COMPLETE | | EQUIPMENT SIZING CALCULATIONS WORKSHEETS. | | | | 2- REVISED A/C PLAN ON SHEET 8.1 NEEDS THE NAME AND | | SIGNATURE OF THE A/C CONTRACTOR WHO SIGNED THE APPROVED | | PLAN AS REQUIRED BY SEC. 107.2.1 CITY AMENDMENTS. NOTE: | | APPROVED PLAN WAS SIGNED BY THE A/C CONTRACTOR MAX AIR | | COOLING, LLC. | | | | 3- OWES $154.50 FOR REVISION RE-SUBMITTAL FEES. NOTE: | | REVISION FEES APPLY ON EVERY RE-SUBMITTAL. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|