2017-11-15 12:03:11RESIDENTIAL (R3) REVISION SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 1- A/C EQUIPMENT SIZING CALCULATIONS SUBMITTED: PROVIDE
 COMPLETE EQUIPMENT SIZING CALCULATIONS "BASED ON
 BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF THE
 BUILDING" AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 NOTE: IT LOOKS LIKE THE EQUIPMENT SIZING CALCULATIONS
 WERE DONE BY THE SAME PERSON WHO DID THE ENERGY
 CALCULATIONS. THE ENERGY CALCULATIONS NEED TO BE
 REVISED. SEE BUILDING REVIEW COMMENTS ON ITEM #1 AND
 REVISE A/C EQUIPMENT SIZING CALCULATIONS AS REQUIRED.
  
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED. SAME
 CALCULATIONS DATED AUGUST 25TH 2017 WERE SUBMITTED.
 AND, ONLY THE SUMMARY PAGES WERE SUBMITTED. NEED THE
 COMPLETE EQUIPMENT SIZING CALCULATIONS. IN ADDITION,
 THE ENERGY CALCULATIONS WERE REVISED ON 10/23/17
 SHOWING THE ACTUAL ORIENTATION OF THE BUILDING, BUT THE
 EQUIPMENT SIZING CALCULATIONS WERE NOT REVISED.
 PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS BASED ON
 THE ACTUAL ORIENTATION OF THE BUILDING AS REQUIRED BY
 SEC. R403.6.1 FBC-ENERGY CONSERVATION.
  
  