Plan Review Notes For Permit 17090467 |
Permit Number |
17090467 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-10-04 19:00:29 | RESIDENTIAL (R3) REVISION MECHANICAL REVIEW COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- A/C EQUIPMENT SIZING CALCULATIONS SUBMITTED: PROVIDE | | COMPLETE EQUIPMENT SIZING CALCULATIONS "BASED ON | | BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF THE | | BUILDING" AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY | | CONSERVATION, 5TH EDITION (2014). | | NOTE: IT LOOKS LIKE THE EQUIPMENT SIZING CALCULATIONS | | WERE DONE BY THE SAME PERSON WHO DID THE ENERGY | | CALCULATIONS. THE ENERGY CALCULATIONS NEED TO BE | | REVISED. SEE BUILDING REVIEW COMMENTS ON ITEM #1 AND | | REVISE A/C EQUIPMENT SIZING CALCULATIONS AS REQUIRED. | | | | | | NOTE: | | THE REVISION FEE OF $207.00 WAS NOT PAID. NEED TO PAY | | FEE NOW BEFORE ANY ADDITIONAL REVIEW IS PERFORMED. | | ADDITIONAL FEES WILL BE CHARGED ON EVERY RE-SUBMITTALS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|