2017-10-04 19:00:29RESIDENTIAL (R3) REVISION MECHANICAL REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
  
 1- A/C EQUIPMENT SIZING CALCULATIONS SUBMITTED: PROVIDE
 COMPLETE EQUIPMENT SIZING CALCULATIONS "BASED ON
 BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF THE
 BUILDING" AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 NOTE: IT LOOKS LIKE THE EQUIPMENT SIZING CALCULATIONS
 WERE DONE BY THE SAME PERSON WHO DID THE ENERGY
 CALCULATIONS. THE ENERGY CALCULATIONS NEED TO BE
 REVISED. SEE BUILDING REVIEW COMMENTS ON ITEM #1 AND
 REVISE A/C EQUIPMENT SIZING CALCULATIONS AS REQUIRED.
  
  
 NOTE:
 THE REVISION FEE OF $207.00 WAS NOT PAID. NEED TO PAY
 FEE NOW BEFORE ANY ADDITIONAL REVIEW IS PERFORMED.
 ADDITIONAL FEES WILL BE CHARGED ON EVERY RE-SUBMITTALS.
  