Plan Review Notes For Permit 17090410 |
Permit Number |
17090410 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-10-24 11:27:01 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE ANCHORING DETAIL, SHEET 1 OF 1 IS NOT PART OF | | THE STATE APPROVED MANUFACTURED BUILDING PLANS. THE | | ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE IS | | REQUIRED ON THE FOUNDATION ANCHORING PLAN. FS 471 AND | | FAC 61G-15-23.003 | | | | | | | | |
|