2017-10-02 14:37:16 | 1ST REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. SHOW ON ENLARGED PLAN GRAB BARS SHALL COMPLY WITH |
| FBC ACC 608.3.2 WHERE A SEAT IS NOT PROVIDED IN |
| STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS, GRAB BARS |
| SHALL BE PROVIDED ON THREE WALLS. GRAB BARS SHALL BE |
| INSTALLED 6 INCHES (150 MM) MAXIMUM FROM ADJACENT |
| WALLS. |
| |
| 2. GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| GRIPPING SURFACE TO FINISHED FLOOR. PER FBC ACC 609.4 |
| |
| 3. DIMENSION MISSING DETAIL #6 SHT. A3 SHALL COMPLY |
| WITH FBC ACC 606.3 HEIGHT. |
| LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 4. SHOW COMPLIANCE FBC ACC 604.7 DISPENSERS. |
| TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| THE CENTERLINE OF THE DISPENSER. |
| |
| 5. LAV SHALL COMPLY WITH FBC PL 416.5 TEMPERED WATER |
| FOR PUBLIC HAND-WASHING FACILITIES. |
| TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| 1070 OR CSA B125.3. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |