2017-10-03 13:45:06 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| PART VIII ELECTRICAL |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. RISER SHOWS A 3 PHASE SERVICE WITH 3 PHASE WIRING |
| GOING TO A SINGLE PHASE PANEL. PLEASE CLARIFY AND/OR |
| CORRECT. FBC 107.2.1 |
| 2. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS |
| STIPULATED IN THE FBC ENERGY CODE. CHANGE OF USE |
| REQUIRES ALL LIGHTING TO MEET THIS CODE. FBC CE |
| 405.2.2, 405.2.2.2 |
| 3. IN THE PANEL SCHEDULES PROVIDED, INDICATE ANY NEW OR |
| ALTERED CIRCUITS. FBC 107.2.1, NEC 408.4 |
| 4. PLAN INDICATES CIRCUITS ON 2ND FLOOR, BUT NO PLAN |
| FOR SECOND FLOOR IS PROVIDED. PROVIDE ELECTRICAL PLAN |
| FOR 2ND FLOOR. FBC 107.2.1 |
| 5. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30 |
| 6. INDICATE THE LIGHTING CIRCUIT FOR EXIT AND EMERGENCY |
| LIGHTS. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE |
| FED FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. NEC |
| 700.12(F) |
| 7. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER |
| ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE |
| CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH |
| CODE. FBC CE 405.5 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |