2017-09-26 08:30:55 | 1ST REVIEW FBC-2014 RESIDIENTIAL MECHANICAL | | PERMIT #17090391 | | 9/26/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE PALM BEACH COUNTY APPRAISERS REPORT INDICATES | | THE RESIDENCE HAS NEVER HAD AN AC SYSTEM, AND THERE IS | | NO RECORD OF A PERMIT FOR A SYSTEM IN THE CITY PERMIT | | FILES. REFER TO SECTION R101.4.5 ENERGY CONSERVATION | | AND SUBMIT AN ENERGY EFFICIENCY COMPLIANCE REPORT FOR | | THE NEW CONDITIONED RESIDENCE. | | | | 2) VERIFY THAT THE NEW AC CLOSET IS IN COMPLIANCE WITH | | SECTION M1305.1.1 FBC-14 RESIDENTIAL: 3" CLEARANCE | | ALONG THE SIDES, BACK AND TOP WITH THE TOTAL WIDTH OF | | THE ENCLOSING SPACE BEING AT LEAST 12" WIDER THAN THE | | AIR HANDLER. | | | | 2) PROVIDE AN ELECTRICAL PLAN. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|