Plan Review Notes For Permit 17090326 |
Permit Number |
17090326 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-09-20 08:21:19 | PERMIT # 17090326 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | FAILED COMMENTS: | | | | 1) SITE PLAN NOT PROVIDED. A SITE PLAN INDICATING | | LOCATION OF TENT(S) IS REQUIRED. | | ***PLEASE NOTE THAT 2 COPIES OF ALL DOCUMENTS ARE | | REQUIRED.*** | | | | 2) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | 3) TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM | | BUILDING STRUCTURES. | | | | 4) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, | | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS | | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. | | | | 5) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | LOCATIONS. | | | | 6) GENERATORS AND OTHER INTERNAL COMBUSTION POWER | | SOURCES SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 | | FEET AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR | | ENCLOSURE. | | | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 804-4751 | | |
|