Plan Review Notes For Permit 17090309 |
Permit Number |
17090309 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-10-18 16:16:02 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17090309 | | 10/18/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M2.1: SMOKE DETECTORS ARE REQUIRED IN THE | | RETURN AIR SYSTEMS OF RTU-3 & 4 PER SECTION 606.2.1. | | PLEASE PROVIDE SYMBOLS ON THE PLAN TO SHOW THE | | LOCATIONS AND PROVIDE SUPERVISORY DETAILS IN ACCORDANCE | | WITH SECTION 606.4.1. | | | | 2) M6.1: PLEASE UPDATE THE ASHRAE 62.1- 2004 REFERENCE | | IN THE O/A TABLE TO 2010. | | | | 3) INDICATE HOW ACCESS TO THE ROOF WILL BE PROVIDED TO | | SERVICE AND REPLACE THE RTU'S- SEE SECTION 306.5. | | | | 4) PROVIDE THE WIND LOAD DESIGN CRITERIA AND | | ENGINEERING FOR TIE DOWN OF THE RTU'S AND CURBS- SEE | | SECTION 301.15. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|