2017-10-18 16:16:021ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17090309
 10/18/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.1: SMOKE DETECTORS ARE REQUIRED IN THE
 RETURN AIR SYSTEMS OF RTU-3 & 4 PER SECTION 606.2.1.
 PLEASE PROVIDE SYMBOLS ON THE PLAN TO SHOW THE
 LOCATIONS AND PROVIDE SUPERVISORY DETAILS IN ACCORDANCE
 WITH SECTION 606.4.1.
  
 2) M6.1: PLEASE UPDATE THE ASHRAE 62.1- 2004 REFERENCE
 IN THE O/A TABLE TO 2010.
  
 3) INDICATE HOW ACCESS TO THE ROOF WILL BE PROVIDED TO
 SERVICE AND REPLACE THE RTU'S- SEE SECTION 306.5.
  
 4) PROVIDE THE WIND LOAD DESIGN CRITERIA AND
 ENGINEERING FOR TIE DOWN OF THE RTU'S AND CURBS- SEE
 SECTION 301.15.
  