Plan Review Notes
Plan Review Notes For Permit 17090309
Permit Number 17090309
Review Stop B
Sequence Number 1
Notes
Date Text
2017-10-02 12:00:272014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17090309
 ADD: 501 FERN ST. SUITE: C
 CONT: HEDRICK BROTHERS
 TEL: 561-267-1309 / TOM HARRY
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. OCT. 02/ 2017
 ACTION: DENIED
  
 1) LIFE SAFETY PLAN ALS1.0:
  
 1A) THE LIFE SAFETY PLAN INDICATES THIS IS A BUSINESS
 OCCUPANCY AND A LEVEL II ALTERATION. PLEASE NOTE THIS
 WILL BE CONSIDERED A CHANGE OF OCCUPANCY. THE LAST
 KNOWN USE THE PALM BEACH COUNTY PROPERTY APPRAISERS
 OFFICE HAS FOR THIS PROPERTY IS 5, 500 SQ. FT. FOR
 UNFINISHED RETAIL AREA. THERE WAS NO CERTIFICATE OF
 OCCUPANCY ISSUED UNDER THE SHELL PERMIT 13030468 NOR
 THE BUILDOUT PERMIT OF 12070649. THE PLANS WILL NEED TO
 BE DESIGNED AS A CHANGE OF OCCUPANCY AND CHAPTER 10 OF
 THE 2014 EXISTING BUILDING CODE AND SECTION 1001.3.1.
 WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION, SECTION 1012 (EXISTING
 BUILDING CODE) SHALL APPLY.
  
 1B) PLEASE NOTE THE DESIGNER OF RECORD HAS DECLARED
 THIS TO BE A BUSINESS OCCUPANCY WITH AN AREA OF
 ASSEMBLY OF 705 SQ. FT. WHERE THE PERCENTAGE OF
 ASSEMBLY USAGE IS OVER THE 10 PERCENT OF THE FLOOR AREA
 BY 0.03 % BUT AN OCCUPANT LOAD OF 47. PLEASE NOTE ONLY
 THE 2 CONFERENCE ROOMS WERE CONSIDERED IN THE
 CALCULATION. THE BREAK ROOM WAS NOT CONSIDERED. WHEN
 THE AREA OF THE BREAK ROOM IS ADDED TO THE ASSEMBLY
 FOOT PRINT THE SQ. FOOTAGE GOES UP TO 0.18%> 10% AND
 THE OCCUPANT LOAD IS INCREASED TO 288/15=19.2 OR 20
 +47= 67 OCCUPANTS. THIS MEETS THE REQUIREMENTS FOR
 MIXED OCCUPANCY UNDER FBC-B 509.3. ALSO SEE THE 2012
 IBC-B COMMENTARY THE BUILDING AREA IS TO BE BASED ON
 THE TENANT SQUARE FOOT AREA WHEN THERE ARE MULTIPLE
 TENANTS ON THE SAME FLOOR LEVEL.
  
 1C) THE DESIGNER OF RECORD SHALL DECLARE IF THE TENANT
 OCCUPANCY SEPARATION IS TO COMPLY WITH WHICH SECTION OF
 THE CODE:
 2014 FBC-B 508.3 NONSEPARATED OCCUPANCIES
 2014 FBC-B 508.3 SEPARATION.
  
 1D) THE LIFE SAFETY PLAN INDICATES THE MEZZANINE LEVEL
 IS DECLARED AN S-2 OCCUPANCY, PLEASE INDICATE THE TYPE
 OF MATERIALS THAT ARE TO BE STORED MAKING THE S2
 STORAGE OCCUPANCY. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 1E) PLEASE NOTE UNDER THE LIFE SAFETY PLAN THE
 MEZZANINE IS LABEL TO HAVE 680 SQUARE FEET. THE 5,500
 SQ. FT. OF AREA FROM THE PROPERTY APPRAISERS OFFICE
 MAYBE LOW. IN TAKING OFF THE SQUARE FOOTAGE FROM THE
 INTERIOR SIDE OF THE EXTERIOR WALLS THE TOTAL SQUARE
 FOOTAGE APPEARS TO BE 6370 SQ. FT. WHEN SCALED. THE 680
 SQUARE FEET OF AREA FOR THE MEZZANINE IS OVER THE
 ALLOWABLE 10% OF THE FLOOR AREA SO IT IS NO LONGER AN
 ACCESSORY OCCUPANCY, PLEASE PROVIDE HOW COMPLIANCE WITH
 :
 2014 FBC-B 508.3 NONSEPARATED OCCUPANCIES
 2014 FBC-B 508.3 SEPARATION.
  
 1F) SINCE THE MEZZANINE IS STORAGE OCCUPANCY AND NOT ON
 GRADE LEVEL, PLEASE PROVIDE HOW THE MEZZANINE WAS
 DESIGNED FOR LIVE LOADS, 2014 FBC-B TABLE 1607.1( 31).
 1G) PLEASE PROVIDE COMPLIANCE WITH LIVE LOAD CONDITIONS
 AND W. P. B. ADMINISTRATIVE CODE FOR LIVE LOADS:
 1G)(1) 106. 1 LIVE LOADS POSTED. WHERE THE LIVE LOADS
 FOR WHICH EACH FLOOR OR PORTION THEREOF OF A COMMERCIAL
 OR INDUSTRIAL BUILDING IS OR HAS BEEN DESIGNED TO
 EXCEED 50 PSF SUCH DESIGN LIVE LOADS SHALL BE
 CONSPICUOUSLY POSTED BY THE OWNER IN THAT PART OF EACH
 STORY IN WHICH THEY APPLY, USING DURABLE SIGNS. IT
 SHALL BE UNLAWFUL TO REMOVE OR DEFACE SUCH NOTICES.
 1G)(2) 106.2 ISSUANCE OF CERTIFICATE OF OCCUPANCY. A
 CERTIFICATE OF OCCUPANCY REQUIRED BY SECTION 111
 SHALL NOT BE ISSUED UNTIL THE FLOOR LOAD SIGNS,
 REQUIRED BY SECTION 106.1, HAVE BEEN INSTALLED.
  
  
 1G)(3) 106.3 RESTRICTIONS ON LOADING. IT SHALL BE
 UNLAWFUL TO PLACE, OR CAUSE OR PERMIT TO BE PLACED, ON
 ANY FLOOR OR ROOF OF A BUILDING, STRUCTURE OR PORTION
 THEREOF, A LOAD GREATER THAN IS PERMITTED BY THIS
 CODE.
  
 1H) THE LIFE SAFETY PLAN SHOW IN THE LARGE CONFERENCE
 ROOM 14 CHAIRS OR THERE COULD BE 14 OCCUPANTS. THE PLAN
 ALSO SHOWS WHAT APPEARS TO BE SLIDING GLASS DOORS ON 2
 SIDES OF THE CONFERENCE ROOM. UNDER THE 2014 FBC-B
 1008.1.2 DOOR SWING EXCEPTION 9 ONLY ALLOWS MANUALLY
 OPERATED HORIZONTAL SLIDING DOORS WHEN THE OCCUPANT
 LOAD IS 10 OR LESS.
  
 1I) THE LIFE SAFETY SHEET ALSO SHOWS A COFFEE AREA WITH
 22 SEATS. LEASE PROVIDE COMPLIANCE WITH;
 1I)(1) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902. IF THERE PLAN IS TO
 HAVE ADDITIONAL OUTSIDE SEASONAL SEATING PLEASE SHOW ON
 THE PLANS.
  
 1I)(2) 226.2 DISPERSION. DINING SURFACES AND WORK
 SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 1I)(3) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ABA SCOPING
 PROVISIONS, EMPLOYEE WORK STATIONS.
  
 1I)(3)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR
 FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 1I)(3))(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES
 AND WORK SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM
 AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR
 OR GROUND.
  
 1J) THE STORAGE/ I. T. ROOM DOOR DOES NOT HAVE THE
 REQUIRED 18 INCHES ON THE LATCH SIDE OF THE DOOR.
 ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES.
 MINIMUM MANEUVERING CLEARANCES AT DOORS SHALL COMPLY
 WITH 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE
 FULL WIDTH OF THE DOORWAY AND THE REQUIRED LATCH SIDE
 OR HINGE SIDE CLEARANCE.
  
 2) SHEET A1.0.1 AND SHEET A6.01 DETAIL 5 WILL NEED TO
 SHOW FOR THE DECORATIVE CEILING ASSEMBLY WILL COMPLY
 WITH 2014 FBC-B 803.11.2.
  
 3) SHEET A.6.0.1 DETAIL 10 SHOWS A DETAIL FOR NEW
 SKYLIGHTS. SHEET A1.0.3 SHOWS (2) SKYLIGHTS AND A NOTE
 7.
 THE STRUCTURAL SHEETS SHOW ON S4 A TYPICAL ROOF OPENING
 DETAIL. THE DETAIL STATES SEE MECHANICAL SHEETS FOR
 OPENING SIZE. THERE IS NO DETAILS OR SIZING FOR THE
 PROPOSED SKYLIGHT. SHEET S1 THE ROOF FRAMING PLAN DOES
 NOT PROVIDE LOCATION NOR SIZE OF THE OPENING.
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (F) SKYLIGHTS.
  
 4) SHEET A3.01 SHOWS NEW WINDOW OPENINGS FOR THE NORTH
 SIDE OF THE BUILDING. THE BUILDING IS BUILT WITHIN ONE
 FOOT OF THE PROPERTY LINE, ALMOST ON THE PROPERTY LINE.
 THERE IS A 14 FOOT ALLEY WAY, YOU CAN TAKE 7 FEET OF
 THE ALLEY WAY FOR OPENINGS BASED ON FIRE SEPARATION
 DISTANCE IN TABLE 705.8. OF THE FBC-B. FOR UNPROTECTED
 , SPRINKLERED YOU CAN HAVE 25 % ALLOWABLE OPENINGS FOR
 THIS SIDE OF THE BUILDING, THE WHOLE BUILDING NOT JUST
 THIS TENANT SPACE, PLEASE PROVIDE COMPLIANCE.
  
 5) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 6) IDENTIFY GLAZING/ MULLIONS.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 7) THRESHOLDS ACCESS. CODE 404.2.5. THRESHOLDS, IF
 PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH (13 MM) HIGH
 MAXIMUM. RAISED THRESHOLDS AND CHANGES IN LEVEL AT
 DOORWAYS SHALL COMPLY WITH 302 AND 303.
  
 8) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  