2017-10-12 08:13:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 THE ELECTRICAL RISERS PROVIDED ARE NOT CLEAR AS TO
 FUNCTION AND LACK INFORMATION. FURTHER PLAN REVIEW
 COMMENTS ARE POSSIBLE.
  
 1. PROVIDE LOAD CALCULATION FOR ATS-1 AND ATS-2 TO
 CONFIRM CAPACITY OF GENERATOR IS SUFFICIENT FOR THE
 ADDITIONAL LOAD FROM ATS-2. IT APPEARS THAT ATS-1 IS
 ALSO FEEDING THE FIRE PUMP? IF THIS IS THE CASE, IS THE
 TRANSFER SWITCH RATED FOR FIRE PUMP USE? GENERATOR MUST
 HAVE CAPACITY FOR THE LOCKED ROTOR CURRENT OF THE FIRE
 PUMP IN ADDITION TO ALL OTHER LOADS. PROVIDE COMPLETE
 LOAD CALCULATION. ALSO NEED FURTHER INFORMATION ON FIRE
 PUMP FEED, WHICH SHOULD NOT BE FED FROM A PANEL THAT
 FEEDS OTHER LOADS. NEC 700.4, 702.4(B)(2), 695.4(A),
 695.4(B)(3). FBC 107.2.1
 2. IS ATS-1 BEING FED FROM TWO 1200 AMP PANELS AND THEN
 FEEDING ANOTHER 1200 AMP PANEL WITH A 600 AMP FEED? OR
 IS IT THE OTHER WAY AROUND? PROVIDE CLARIFICATION. FBC
 107.2.1
 3. SHOW FEEDER CONDUIT AND WIRE SIZE TO ATS-1 FROM
 GENERATOR. FBC 107.2.1; NEC 310.15(B)(16)
 4. WHY IS THE EMERGENCY FEED TO ATS-2, WHICH IS 200
 AMP, ONLY SIZED AT 60 AMP? IS THE BREAKER FROM THE
 NORMAL SOURCE A 200 AMP OR A 150 AMP? WIRE SIZE STATED
 AS 2/0 IS NOT RATED FOR 200 AMP. PROVIDE CLARIFICATION
 AND/OR CORRECTION. FBC 107.2.1; NEC 310.15(B)(16)
 5. PROVIDE COPY OF CONTRACT WITH SCOPE OF WORK AND
 VALUE OF WORK LISTED. FBC 109.3
 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 7. PROVIDE AIC RATING OF EACH ATS. INDICATE ON SPEC
 SHEETS WHICH MODEL IS BEING INSTALLED. NEC 110.3, 110.9
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER