2018-02-26 14:54:22PROVISO: PERMIT # 17090199
 PLUMBING COMMENTS TO BE CORRECTED AND APPROVED REVISED
 PLAN SHEETS ON JOBSITE FOR FIRST ROUGH INSPECTION.
 1. THE SANITARY ISOMETRIC DOES NOT MATCH THE FLOOR PLAN
 IT SHOWS 2 SOIL STACKS NEAR THE ELEVATOR SUMP THAT ARE
 NOT SHOWN ON THE FLOOR PLAN PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
 2. THE FIRST TWO SECTIONS OF 8" PIPE ON THE STORM
 ISOMETRIC ARE UNDERSIZED THEY SHOULD BE 10". PER FBC PL
 TABLE 1006.3 1/8' PFT
 3. THE NEW SHEETS P3.2.1 AND P3.3.1 ARE MISSING FROM
 ONE OF THE PLAN SETS. PER WPB AMEND TO FBC 107.2.1
 4. IF THE GREASE INTERCEPTORS ARE TO BE APPROVED UNDER
 THIS PLAN SET PLEASE PROVIDE THE FOLLOWING.
 A) PROVIDE SIZING CALCULATIONS FROM SCHEIR
 MANUFACTURING FOR THE GREASE INTERCEPTORS. PER WPB
 AMEND TO FBC 107.2.1
 B) SHT. PF2.1.1 A DOUBLE SANITARY TEE CANNOT BE USED AS
 A SAMPLING PORT A PRE MANUFACTURED SAMPLING PORT OR A
 TWO WAY CLEANOUT CAN BE USED PER WPB UTILITIES DEPT.
 SEE STANDARD DETAIL GS 7 OR GS 7.1
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  