Plan Review Notes
Plan Review Notes For Permit 17090199
Permit Number 17090199
Review Stop P
Sequence Number 2
Notes
Date Text
2018-02-13 11:45:572ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE SANITARY ISOMETRIC DOES NOT MATCH THE FLOOR PLAN
 IT SHOWS 2 SOIL STACKS NEAR THE ELEVATOR SUMP THAT ARE
 NOT SHOWN ON THE FLOOR PLAN PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 2. THE FIRST TWO SECTIONS OF 8" PIPE ON THE STORM
 ISOMETRIC ARE UNDERSIZED THEY SHOULD BE 10". PER FBC PL
 TABLE 1006.3 1/8' PFT
  
 3. THE NEW SHEETS P3.2.1 AND P3.3.1 ARE MISSING FROM
 ONE OF THE PLAN SETS. PER WPB AMEND TO FBC 107.2.1
  
 4. IF THE GREASE INTERCEPTORS ARE TO BE APPROVED UNDER
 THIS PLAN SET PLEASE PROVIDE THE FOLLOWING.
  
 A) PROVIDE SIZING CALCULATIONS FROM SCHEIR
 MANUFACTURING FOR THE GREASE INTERCEPTORS. PER WPB
 AMEND TO FBC 107.2.1
  
 B) SHT. PF2.1.1 A DOUBLE SANITARY TEE CAN NOT BE USED
 AS A SAMPLING PORT A PRE MANUFACTURED SAMPLING PORT OR
 A TWO WAY CLEANOUT CAN BE USED PER WPB UTILITIES DEPT.
 SEE STANDARD DETAIL GS 7 OR GS 7.1
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  