2018-02-27 14:11:34 | RECEIVED CORRECTION AND CHANGED STATUS TO PASSED. |
| |
| |
2018-02-08 10:39:59 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| PART VIII ELECTRICAL |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| THIS REVIEW FOR FOUNDATION PERMIT ONLY. |
| |
| RESPONSE LETTER STATED THAT SHEET E3.0.0 WAS PROVIDED |
| TO ADDRESS COMMENTS. HOWEVER, THE SHEET WAS ONLY |
| PROVIDED FOR 2 OF THE 3 SETS. THIS SHEET IS REQUIRED |
| FOR EACH SET. (FBC 107.2.1) THE PREVIOUS COMMENT IS |
| LISTED BELOW, AND THERE IS A NEW COMMENT THAT FOLLOWS |
| BASED ON THE SUBMISSION PROVIDED. |
| |
| 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| SERVICE EQUIPMENT, WIRE AND BREAKER SIZES FOR SERVICE. |
| SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING |
| TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94, |
| 408.30, 695.3; FBC 107.2.1 |
| |
| NEW COMMENT: |
| |
| 2. PLAN STATES THAT THE FEED TO THE RETAIL WIREWAY IS 2 |
| SETS OF 500 KCMIL ALUMINUM, WHICH IS RATED FOR A TOTAL |
| OF 620 AMPS. THIS WIRE WILL BE FUSED AT 800 AMPS, SO |
| THE WIRE IS UNDERSIZED. PROVIDE CORRECTION. THIS |
| COMMENT WILL NOT HOLD UP THE FOUNDATION PERMIT, BUT |
| NEEDS TO BE CORRECTED. NEC 310.15(B)(16) |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |