2017-09-20 09:16:04 | 201 NORTH FLAGLER DRIVE - RESTAURANT |
| PERMIT #17090199 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| **RETAIL/RESTAURANT FOUNDATION ONLY** |
| |
| FIRE PROTECTION BACKFLOW PREVENTERS: PER NFPA 24 |
| SECTION 6.2.1, ALL CONNECTIONS TO PRIVATE FIRE SERVICE |
| MAINS FOR FIRE PROTECTION SYSTEMS SHALL BE ARRANGED IN |
| ACCORDANCE WITH ONE OF THE FOLLOWING SO THAT THEY CAN |
| BE ISOLATED: |
| (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40 |
| FEET FROM THE BUILDING. |
| (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST |
| INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED |
| CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE |
| BUILDING AS THE HEIGHT OF THE WALL FACING THE POST |
| INDICATOR VALVE. |
| (2) A WALL POST INDICATOR VALVE |
| (3) AN INDICATING VALVE IN A PIT, INSTALLED IN |
| ACCORDANCE WITH SECTION 6.4 |
| (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING |
| VALVE NOT LESS THAN 40 FEET FROM THE BUILDING. |
| (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A |
| BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE |
| SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET |
| BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF |
| THE WALL FACING THE BACKFLOW PREVENTER. |
| (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM |
| ACCESSIBLE FROM THE EXTERIOR |
| (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE |
| ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE |
| AUTHORITY HAVING JURISDICTION |
| |
| THE CITY OF WEST PALM BEACH REQUIRES CONSTRUCTION |
| TRAILERS LARGER THAN A SINGLE "DOUBLE WIDE" (OR TWO |
| "SINGLE WIDE") TO EITHER BE PROTECTED BY AN AUTOMATIC |
| SPRINKLER SYSTEM OR COMPLY WITH THE SEPARATION |
| REQUIREMENTS OF NFPA 241. TEMPORARY CONSTRUCTION |
| TRAILERS OR MODULAR BUILDINGS WILL REQUIRE A PERMIT AND |
| COMPLIANCE WITH THE FOLLOWING: |
| PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, |
| ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: |
| TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF |
| COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE |
| CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, |
| TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. |
| PER TABLE 4.2.1: |
| 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| |
| WESLEY JOLIN |
| ASSISTANT FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |