Plan Review Notes For Permit 17090196 |
Permit Number |
17090196 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-11-17 10:12:04 | FOLLOWING COMMENTS (2) ADDED TO PLAN AS PROVISO: | | | | 1. RISER DIAGRAM AND PANEL SCHEDULES PROVIDED SHOW THE | | HIGH LEG ON PHASE C. HIGH LEG IS REQUIRED TO BE ON | | PHASE B PER THE NEC. PROVIDE CORRECTION FOR RISER AND | | PANEL SCHEDULES. NEC 408.3(E) | | 2. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF | | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND | | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|