Plan Review Notes
Plan Review Notes For Permit 17090196
Permit Number 17090196
Review Stop E
Sequence Number 2
Notes
Date Text
2017-11-17 10:12:04FOLLOWING COMMENTS (2) ADDED TO PLAN AS PROVISO:
  
 1. RISER DIAGRAM AND PANEL SCHEDULES PROVIDED SHOW THE
 HIGH LEG ON PHASE C. HIGH LEG IS REQUIRED TO BE ON
 PHASE B PER THE NEC. PROVIDE CORRECTION FOR RISER AND
 PANEL SCHEDULES. NEC 408.3(E)
 2. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  