Plan Review Notes
Plan Review Notes For Permit 17090196
Permit Number 17090196
Review Stop M
Sequence Number 1
Notes
Date Text
2017-09-22 10:08:281ST REVIEW FBC-2014 MECHANICAL , EXISTING BUILDING
 CODES
 PERMIT #17090196
 9/122/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE MECHANICAL PLANS SHOWING ALL REQUIRED
 ALTERATIONS TO THE SYSTEMS TO ACCOMODATE THE FLOOR PLAN
 CHANGES.
  
 2) THE ARCHITECT SHALL PROVIDE ORIGINAL SEALS AND
 SIGNATURES TO THE PLANS- SECTION 61G15- 16.003 FLORIDA
 AMINISTRATIVE CODE.
  
 3) A MINIMUM OF TWO SETS OF PLANS ARE REQUIRED PER
 SECTION 107.2.1 WPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  