Plan Review Notes For Permit 17090144 |
Permit Number |
17090144 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2017-10-18 08:41:35 | RESIDENTIAL (R3) RE-ROOF THIRD BUILDING REVIEW | | CHECKLIST. | | CODE: FBC 5TH EDITION (2014). | | | | 1- ENGINEER TO REVISE THE RAS 117 CALCULATIONS | | SUBMITTED: | | | | A) THE FASTENING SPECIFIED ON THE THE SELECTED ASSEMBLY | | ON PAGE 14 OF NOA 17-0222.09 AND THE FASTENING | | SPECIFIED ON RAS 117 CALCULATIONS SUBMITTED DON'T | | MATCH. NOA SHOWS THREE ROWS OF FASTENERS IN THE CENTER | | OF THE SHEET, WHILE ENGINEER CALCULATIONS SHOW TWO | | ROWS. REVISE AS REQUIRED TO MATCH. NOTE: CLEARLY SHOW | | NUMBER OF ROWS REQUIRED FOR THE PERIMETER AND CORNER | | AREAS ON THE ENHANCED FASTENING PATTERN. SEC. 8.1 OF | | RAS 117. | | | | B) NOA 17-0222.09 SHOWS THE FASTENER SPACING TO BE AT | | 6"O.C. ENGINEER CHANGED THE FASTENER SPACING TO 7"O.C. | | FOR FIELD ZONE. ACCORDING TO RAS 117 SEC. 8.1 THE | | FASTENING SPACING SHOWN ON THE NOA SHALL BE APPLICABLE | | TO THE FIELD ZONE. THEREFORE, IT CAN NOT BE CHANGED. | | ENGINEER TO REVISE FASTENER SPACING AS REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|