Plan Review Notes
Plan Review Notes For Permit 17090144
Permit Number 17090144
Review Stop B
Sequence Number 3
Notes
Date Text
2017-10-18 08:41:35RESIDENTIAL (R3) RE-ROOF THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- ENGINEER TO REVISE THE RAS 117 CALCULATIONS
 SUBMITTED:
  
 A) THE FASTENING SPECIFIED ON THE THE SELECTED ASSEMBLY
 ON PAGE 14 OF NOA 17-0222.09 AND THE FASTENING
 SPECIFIED ON RAS 117 CALCULATIONS SUBMITTED DON'T
 MATCH. NOA SHOWS THREE ROWS OF FASTENERS IN THE CENTER
 OF THE SHEET, WHILE ENGINEER CALCULATIONS SHOW TWO
 ROWS. REVISE AS REQUIRED TO MATCH. NOTE: CLEARLY SHOW
 NUMBER OF ROWS REQUIRED FOR THE PERIMETER AND CORNER
 AREAS ON THE ENHANCED FASTENING PATTERN. SEC. 8.1 OF
 RAS 117.
  
 B) NOA 17-0222.09 SHOWS THE FASTENER SPACING TO BE AT
 6"O.C. ENGINEER CHANGED THE FASTENER SPACING TO 7"O.C.
 FOR FIELD ZONE. ACCORDING TO RAS 117 SEC. 8.1 THE
 FASTENING SPACING SHOWN ON THE NOA SHALL BE APPLICABLE
 TO THE FIELD ZONE. THEREFORE, IT CAN NOT BE CHANGED.
 ENGINEER TO REVISE FASTENER SPACING AS REQUIRED.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]