Plan Review Notes
Plan Review Notes For Permit 17090144
Permit Number 17090144
Review Stop B
Sequence Number 1
Notes
Date Text
2017-09-07 10:46:59RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCEMENT AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 17-0222.09 SUBMITTED. NEED THE CALCULATIONS TO MEET THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 2- PROVIDE ROOF SKETCH SHOWING THE TOTAL FLAT ROOF AREA
 AS REQUIRED BY CITY OF WEST PALM BEACH POLICY FOR
 RE-ROOF PERMITS. ALSO, SPECIFY THE MEAN ROOF HEIGHT.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712