Plan Review Notes
Plan Review Notes For Permit 17090104
Permit Number 17090104
Review Stop M
Sequence Number 2
Notes
Date Text
2017-11-08 10:16:01PLAN DENIED
 1) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS
 ALL INFORMATION, DRAWINGS,SPECIFICATIONS AND
 ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE
 FOR THE DESIGN. FBC 2014
 2) REFER TO SECTION R403.2.4 AIR HANDLING UNITS
 2014 FLORIDA ENERGY CODE. IF AIR HANDLERS ARE GOING
 INTO ATTIC.
 ALSO SHOW RETURN AIR DUCT AND SIZE TO RETURN AIR PLENUM
  
 CALLED STEPHANIE LEFT A MESSAGE TO CALL ME.
  