2017-09-18 09:48:361) SHT. 2 OF 3 - PIPING DIAGRAM - SHOWS A 2 INCH MAIN
 DRAIN TO THE EXISTING POOL PUMP AND ALSO SHOWS A 3 INCH
 MAIN DRAIN CONNECTED TO THE PUMP, FILTER AND HEATER.
 CLARIFY.
 2) SHT.2 OF 3 - THE PIPING DIAGRAM SHOWS A 3 INCH
 RETURN TO THE SPA CONNECTED TO THE 2 HP BLOWER AND THE
 PIPING DIAGRAM ALSO SHOWS A 2 INCH RETURN TO THE SPA
 FROM THE EXISTING POOL PUMP. CLARIFY.
 3) SHT. 2 OF 3 - THE SKIMMER AND VAC DETAIL SHOWS A 3
 INCH RETURN TO THE SPA AND THE PIPING DIAGRAM SHOWS A 3
 INCH AND ALSO A 2 INCH RETURN TO THE SPA. CLARIFY.
 4) SHT. 3 OF 3 - THERE IS A AREA ON THE PLAN LABELED AS
 " ASPS-15" BUT ALL THE ITEMS IN THIS AREA ARE BLANK.
 CLARIFY.
 5) THE PLAN SHOWS AN EXISTING PUMP BUT SPECS HAVE BEEN
 SUBMITTED FOR A NEW PUMP. CLARIFY.
  
 I AM CONFUSED AS TO THIS PIPING ARRANGEMENT .PLEASE
 SUBMIT A NARRATIVE THAT EXPLAINS THIS PIPING
 ARRANGEMENT.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  