Plan Review Notes For Permit 17090100 |
Permit Number |
17090100 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-09-18 09:48:36 | 1) SHT. 2 OF 3 - PIPING DIAGRAM - SHOWS A 2 INCH MAIN | | DRAIN TO THE EXISTING POOL PUMP AND ALSO SHOWS A 3 INCH | | MAIN DRAIN CONNECTED TO THE PUMP, FILTER AND HEATER. | | CLARIFY. | | 2) SHT.2 OF 3 - THE PIPING DIAGRAM SHOWS A 3 INCH | | RETURN TO THE SPA CONNECTED TO THE 2 HP BLOWER AND THE | | PIPING DIAGRAM ALSO SHOWS A 2 INCH RETURN TO THE SPA | | FROM THE EXISTING POOL PUMP. CLARIFY. | | 3) SHT. 2 OF 3 - THE SKIMMER AND VAC DETAIL SHOWS A 3 | | INCH RETURN TO THE SPA AND THE PIPING DIAGRAM SHOWS A 3 | | INCH AND ALSO A 2 INCH RETURN TO THE SPA. CLARIFY. | | 4) SHT. 3 OF 3 - THERE IS A AREA ON THE PLAN LABELED AS | | " ASPS-15" BUT ALL THE ITEMS IN THIS AREA ARE BLANK. | | CLARIFY. | | 5) THE PLAN SHOWS AN EXISTING PUMP BUT SPECS HAVE BEEN | | SUBMITTED FOR A NEW PUMP. CLARIFY. | | | | I AM CONFUSED AS TO THIS PIPING ARRANGEMENT .PLEASE | | SUBMIT A NARRATIVE THAT EXPLAINS THIS PIPING | | ARRANGEMENT. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|