Plan Review Notes
Plan Review Notes For Permit 17090058
Permit Number 17090058
Review Stop M
Sequence Number 1
Notes
Date Text
2017-09-22 17:37:481ST REVIEW FBC-2014 MECHANICAL, WPB AMENDMENTS TO THE
 FBC.
 REVISION #17090058
 MASTER PERMIT #15111020
 THE BRISTOL
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC CLOSET DOORS UO5G, UO5H, & UO5K MUST BE
 NON-COMBUSTIBLE- SECTION 602.2.1. THE DOOR SCHEDULE ON
 THE MASTER SHEET A8.12 INDICATES WOOD DOORS.
  
 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE
 COOKING APPLIANCE IN THE KITCHEN AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS WITH APPROVAL STAMP AND
 SIGNATURE BY THE EOR- SECTION 623.1- 623.5 FBC-14 FUEL
 GAS.
  
 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE
 EXHAUST VENTILATION HOOD AND EXHAUST DUCT, AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS WITH APPROVAL STAMP AND
 SIGNATURE BY THE EOR- SECTIONS 505.1 AND 505.2.
  
 4) SHEET M2.90-15B: PLEASE LABEL THE ROOMS ON THE
 REVISED PLAN.
  
 5) SHOW THE LOCATIONS OF THE RETURN OPENINGS AT THE
 PERIMETER COVES AND PROVIDE A DETAIL. PLEASE NOTE THAT
 ALL AIR SUPPLIED TO A MASTER SUITE MUST BE RETURNED-
 SECTION 601.5 (3).
  
 6) PROVIDE SUBDUCT INSTALLATION DETAILS.
  
 7) THE UPLOADED NARRATIVE STATES "REMOVED EXHAUST
 FANS". PLEASE CLARIFY WHICH EXHAUST FANS HAVE BEEN
 REMOVED.
  