Plan Review Notes
Plan Review Notes For Permit 17090024
Permit Number 17090024
Review Stop P
Sequence Number 1
Notes
Date Text
2017-09-19 14:16:41DENIED AS FOLLOW;
  
 1. SPECIFICATION FOR PLUMBING CODE COMPLIANCE SAY 2010
 FPC ON PAGE P-0.0.00 BUT ON PAGE A-0.0.00 IT REFERS TO
 FBC RESIDENTIAL 2014. PLEASE REFLECT AND MAKE
 CORRECTION. UNDER GENERAL NOTES P-0.0.00 IT REFERS TO
 COMMERCIAL WORK COMPLIANCE WHEN THE RESIDENTIAL IS
 STATED OTHER PAGES. FBC AMENDMENTS 107.2.1
 2. LAY OUT ON PLAN NOT TO CODE, PLEASE PROVIDE AN
 ISOMETRIC DIAGRAM. SHOWER EXCEEDS LENGTH ON TRAP AND
 VENTING. PLEASE IDENTIFY ALL PIPE AND FIXTURES ON
 LAYOUT AND ISOMETRIC. DRAIN, WASTE AND VENT PIPE SIZING
 AND RISER DIAGRAM OF ALL FIXTURES NEED TO BE LABELED;
 FBC P3004, P3005, FBC AMENDMENTS 107.5.3.
 3. BAR SINK OUTSIDE IN THE BACK HAS WATER TO IT BUT NO
 DRAIN WASTE AND VENT. P3004, P3005,
 4. SHOW CLEAN OUT ON 3? RISER STACK TO SECOND FLOOR AND
 OUTSIDE OF BUILDING, SIZE CORRECTLY, P-3.1.00. FBC
 AMENDMENTS P3005.2
 5. WASHING MACHINE DOWN STAIRS NEED TO BE ON STAND PIPE
 AND VENTED, WASHING MACHINE SHOWN UP STAIR, WATER SHOWN
 ON PLAN BUT NO DWV, LAUNDRY TRAY SHOW FLOOR TYPE BUT
 SPECS SHOW A MUSTEE FREE STANDING TYPE SEE PAGE AND
 VENT TO CODE. P-1.4.01. FBC P3004, P3005.
 6. SHOW SHUT OFF VALVE FOR WATER SERVICE COMING IN THE
 HOUSE ON ISOMETRIC PAGE P-3.0.00. FBC P290.9.4
 7. DETAIL FOR ISLAND SINK ON PAGE P-4.0.00 SHOWS CLEAN
 OUT BUT NEED TO SHOW AIR ADMITTANCE VALVE WHERE CLEAN
 OUT IS TO REFLECT PLUMBING ISOMETRIC. FBC P3114.4
 8. SHOWS A GAS GRILL OUTSIDE A GAS PERMIT AND
 APPLICATION NEEDS TO BE FILED WITH A QUALIFIED LICENSED
 CONTRACTOR. FBC AMENDMENTS 105.1
 9. FAUCET IN MASTER VALVE SHALL HAVE A TEMPERED MIXING
 VALVE. IF INTEGRAL PROVIDE SPECIFICATION OR LOCATION
 WHERE IT WILL BE PLACED FBC P2724.1
 10. ANY PIPE GOING THROUGH A FOUNDATION MUST BE SLEEVED
 TO PREVENT COMPRESSION OF PIPE THROUGH FOOTER AND MUST
 BE SLEEVED TWO PIPE SIZE LARGER. FBC P2603.4
  