2017-09-14 13:51:57 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| PART VIII ELECTRICAL |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE COMPLETED PANEL SCHEDULE. CURRENTLY, PANEL |
| SCHEDULE DOES NOT SHOW ANY LOADS FOR EACH CIRCUIT, DOES |
| NOT SHOW WIRE SIZE, AND DOES NOT INDICATE AFCI OR GFCI |
| PROTECTION. PROVIDE CORRECTION. NEC 210.8, 210.12, |
| 215.5, 408.4; FBC RE3706.2, RE3902; FBC 107.2.1 |
| 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. NEC 250.94; FBC RE3609.3 |
| 3. SERVICE DISCONNECT ON POWER PLAN IS SHOWN AS |
| NON-FUSED. OVERCURRENT PROTECTION IS REQUIRED AT THIS |
| LOCATION. PROVIDE CORRECTION. NEC 230.91; FBC RE |
| 3603.3.3 |
| 4. NOTE 6 STATES "PROVIDE ARC FAULT RECEPTACLES AS PER |
| NEC 210.12". CODE REQUIRES THE FOLLOWING: "ALL |
| 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH |
| CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY |
| ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, |
| HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI |
| PROTECTION". PROVIDE CORRECTION TO INCLUDE MORE THAN |
| RECEPTACLES. NEC 210.12; FBC RE3902.12 |
| 5. DUE TO THE TYPE OF LIGHT FIXTURES NOT CLARIFIED IN |
| CLOSETS, PROVIDE NOTE THAT LIGHT FIXTURES SHALL COMPLY |
| WITH NEC 410.16. NEC 410.16; FBC RE4003.12 |
| 6. DUE TO THE TYPE OF LIGHT FIXTURES NOT CLARIFIED IN |
| DAMP LOCATIONS, PROVIDE NOTE THAT LIGHT FIXTURES SHALL |
| COMPLY WITH NEC 410.10. NEC 410.10(D); FBC RE4003.11 |
| 7. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC CE R404.1 |
| 8. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 |
| 9. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS, |
| FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, |
| WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1 |
| 10. THE COVERED PATIO SHOWS 2 GFCI STANDARD OUTLETS IN |
| SUMMER KITCHEN. THESE OUTLETS ARE REQUIRED TO BE |
| WEATHER PROOF. PROVIDE CORRECTION. NEC 406.9; FBC RE |
| 4002.8 |
| 11. CODE STATES: "FOR DWELLING UNITS, ATTACHED GARAGES, |
| AND DETACHED GARAGES WITH ELECTRIC POWER, AT LEAST ONE |
| WALL SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE |
| INSTALLED ON THE EXTERIOR SIDE OF OUTDOOR |
| ENTRANCES/EXITS WITH GRADE LEVEL ACCESS". SOME OF THE |
| ENTRY/EXITS DO NOT SHOW A SWITCH TO OUTSIDE LIGHTS. |
| PROVIDE CORRECTION. NEC 210.70(A)(2)(B), FBC RE3903.3 |
| 12. THE WATER HEATER SPECIFIED ON SHEET P.0.0.00 IS |
| SHOWN WITH 4500 WATT ELEMENTS. THE PANEL SCHEDULE SHOWS |
| A 35 AMP BREAKER FOR THIS UNIT, WHICH IS TOO LARGE PER |
| CODE. BREAKER SHOULD BE SIZED AT 125% OF THE LOAD, |
| WHICH WOULD BE A 25 AMP BREAKER. PROVIDE CORRECTION. |
| NEC 422.13; FBC RE3702.10 |
| 13. CIRCUITS D-6,8 AND D-13,15 SHOW A 30 AMP DISCONNECT |
| WITH 25 AMP FUSES. THE SPECS ON SHEET M-1 STATE THAT |
| THE MOCP IS 30 AMPS FOR EACH UNIT. THE AMPACITY OF THE |
| CONDUCTORS SUPPLYING MULTIMOTOR AND COMBINATION LOAD |
| EQUIPMENT SHALL NOT BE LESS THAN THE MINIMUM CIRCUIT |
| AMPACITY MARKED ON THE EQUIPMENT. THE BRANCH CIRCUIT |
| OVERCURRENT PROTECTION DEVICE RATING SHALL BE THE SIZE |
| AND TYPE MARKED ON THE EQUIPMENT. PROVIDE CORRECTION. |
| NEC 440.22(C); FBC RE3702.11 |
| 14. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| PER CODE. FBC R314.3, R315.1; FBC 107.2.1 |
| 15. LIGHT FIXTURE OVER MASTER SHOWER IS NOT VP. PROVIDE |
| CORRECTION. NEC 410.10(D); FBC RE4003.11 |
| 16. LAUNDRY ROOM ON 2ND FLOOR DOES NOT SHOW ANY OUTLETS |
| FOR WASHER OR DRYER AND CIRCUITRY IS NOT INCLUDED IN |
| PANEL SCHEDULE. PROVIDE CORRECTION. FBC 107.2.1 |
| 17. RECEPTACLES FOR GARAGE DOOR OPENERS, CIRCUITS D-40 |
| AND D-41, REQUIRE GFCI PROTECTION. PROVIDE CORRECTION. |
| NEC 210.8; FBC RE3902.2 |
| |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |