Plan Review Notes For Permit 17090023 |
Permit Number |
17090023 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2017-12-28 06:39:21 | 1) SHT.P.1.3.00C - NOTE #2 STATES THAT THE T & P LINE | | FROM THE WATER HEATER SHALL DISCHARGE TO MOP SINK BUT | | THERE IS NO MOP SINK SHOWN ON THE FLOOR PLAN OR THE | | WATER OR SANITARY RISER. NOTE - THE DISCHARGE TO A MOP | | SINK IS NOT A SUITABLE LOCATION AS INJURY TO A BUILDING | | OCCUPANT COULD OCCUR IF THE VALVE DISCHARGES. 2014 FBCR | | SEC. P2803.6.1. | | 2) SHT. P.3.0.00C - PART OF THE WATER RISER IS MISSING. | | 3) SHT. P.3.1.00C - SIZE ALL DRAINS, STACKS AND VENTS. | | WPB AMEND. TO FBC SEC. 107.2.1. | | 4)THE WATER HEATER IN THE GARAGE SHALL BE PROTECTED | | FROM PHYSICAL DAMAGE. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | |
|