Plan Review Notes
Plan Review Notes For Permit 17090023
Permit Number 17090023
Review Stop P
Sequence Number 1
Notes
Date Text
2017-09-19 15:43:06DENIED 9/19/17
  
 1. SPECIFICATION FOR PLUMBING CODE COMPLIANCE SAY 2010
 FPC ON PAGE P-0.0.00C BUT ON PAGE A-0.0.00 IT REFERS TO
 FBC RESIDENTIAL 2014. PLEASE REFLECT AND MAKE
 CORRECTION. UNDER GENERAL NOTES P-0.0.00C IT REFERS TO
 COMMERCIAL WORK COMPLIANCE WHEN THE RESIDENTIAL IS
 STATED OTHER PAGES. FBC AMENDMENTS 107.2.1
 2. LAY OUT ON PLAN NOT TO CODE, PLEASE PROVIDE AN
 ISOMETRIC DIAGRAM. PLEASE IDENTIFY ALL PIPE AND
 FIXTURES ON LAYOUT AND ISOMETRIC. DRAIN, WASTE AND VENT
 PIPE SIZING AND RISER DIAGRAM OF ALL FIXTURES NEED TO
 BE LABELED; FBC P3004, P3005, FBC AMENDMENTS 107.5.3.
 3. WASHING MACHINE NEEDS TO BE ON STAND PIPE AND
 VENTED, LAUNDRY TRAY SHOW FLOOR TYPE BUT SPECS SHOW A
 MUSTEE FREE STANDING TYPE SEE PAGE AND VENT TO CODE.
 P-1.3.00C. FBC P3004, P3005.
 4. SHOW CLEAN OUT ON 2? RISER STACK TO STAND PIPE FOR
 WASHING MACHINE AND REVENT, P-3.1.00. FBC P3005.2.6
 5. SHOWS A GAS GRILL OUTSIDE A GAS PERMIT AND
 APPLICATION NEEDS TO BE FILED WITH A QUALIFIED LICENSED
 CONTRACTOR. FBC AMENDMENTS 105.1
 6. FAUCET IN MASTER VALVE SHALL HAVE A TEMPERED MIXING
 VALVE. IF INTEGRAL PROVIDE SPECIFICATION OR LOCATION
 WHERE IT WILL BE PLACED FBC P2724.1
 7. ANY PIPE GOING THROUGH A FOUNDATION MUST BE SLEEVED
 TO PREVENT COMPRESSION OF PIPE THROUGH FOOTER AND MUST
 BE SLEEVED TWO PIPE SIZE LARGER. P1.3.00C FBC P2603.4
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 561-805-6720
 [email protected]
  
  