Date |
Text |
2017-09-19 15:43:06 | DENIED 9/19/17 |
| |
| 1. SPECIFICATION FOR PLUMBING CODE COMPLIANCE SAY 2010 |
| FPC ON PAGE P-0.0.00C BUT ON PAGE A-0.0.00 IT REFERS TO |
| FBC RESIDENTIAL 2014. PLEASE REFLECT AND MAKE |
| CORRECTION. UNDER GENERAL NOTES P-0.0.00C IT REFERS TO |
| COMMERCIAL WORK COMPLIANCE WHEN THE RESIDENTIAL IS |
| STATED OTHER PAGES. FBC AMENDMENTS 107.2.1 |
| 2. LAY OUT ON PLAN NOT TO CODE, PLEASE PROVIDE AN |
| ISOMETRIC DIAGRAM. PLEASE IDENTIFY ALL PIPE AND |
| FIXTURES ON LAYOUT AND ISOMETRIC. DRAIN, WASTE AND VENT |
| PIPE SIZING AND RISER DIAGRAM OF ALL FIXTURES NEED TO |
| BE LABELED; FBC P3004, P3005, FBC AMENDMENTS 107.5.3. |
| 3. WASHING MACHINE NEEDS TO BE ON STAND PIPE AND |
| VENTED, LAUNDRY TRAY SHOW FLOOR TYPE BUT SPECS SHOW A |
| MUSTEE FREE STANDING TYPE SEE PAGE AND VENT TO CODE. |
| P-1.3.00C. FBC P3004, P3005. |
| 4. SHOW CLEAN OUT ON 2? RISER STACK TO STAND PIPE FOR |
| WASHING MACHINE AND REVENT, P-3.1.00. FBC P3005.2.6 |
| 5. SHOWS A GAS GRILL OUTSIDE A GAS PERMIT AND |
| APPLICATION NEEDS TO BE FILED WITH A QUALIFIED LICENSED |
| CONTRACTOR. FBC AMENDMENTS 105.1 |
| 6. FAUCET IN MASTER VALVE SHALL HAVE A TEMPERED MIXING |
| VALVE. IF INTEGRAL PROVIDE SPECIFICATION OR LOCATION |
| WHERE IT WILL BE PLACED FBC P2724.1 |
| 7. ANY PIPE GOING THROUGH A FOUNDATION MUST BE SLEEVED |
| TO PREVENT COMPRESSION OF PIPE THROUGH FOOTER AND MUST |
| BE SLEEVED TWO PIPE SIZE LARGER. P1.3.00C FBC P2603.4 |
| |