2017-10-02 10:54:481) SUBMIT 2 COPIES THE MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION MANUAL FOR THE TANKLESS WATER HEATER.
 2ND REQUEST. 2014 FBC-FUEL GAS SEC.402.2, 301.3.
 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE GAS
 APPLIANCES. THE AIR DEDICATED FOR THE HOOD CANNOT BE
 USED FOR COMBUSTION AIR FOR THE GAS APPLIANCES. 2014
 FBC-FUEL GAS SEC.304.9.3,
  